MCR temperature transducer for Pt 100 temperature sensors, configured via DIP switch, with screw connection, not pre-configured
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2864273 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Height 93.1 mm
- Ambient temperature (operation) -20 °C ... 65 °C
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Number of outputs 1
- Ripple < 20 mVPP (at 10 kΩ)
- Short-circuit current approx. 10 mA
- Stripping length 12 mm
- Conductor cross section flexible 0.2 mm² ... 2.5 mm²
- Maximum temperature coefficient < 0.02 %/K
- Color green
- Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
- Configurable/programmable Yes, unconfigured
- Load/output load voltage output ≥ 10 kΩ
- Supply voltage range 19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
- Power consumption < 500 mW
- Protective circuit Transient protection
- Overvoltage category II
- ECLASS 9.0 27210129
- Depth 101.2 mm
- Permissible humidity (operation) 5 % ... 95 % (non-condensing)
- Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
- Voltage output signal 0 V ... 10 V
- Max. current consumption < 21 mA (at 24 V DC)
- Conductor cross section solid 0.2 mm² ... 2.5 mm²
- No. of channels 1
- Maximum altitude ≤ 2000 m
- Sensor input current 1 mA (constant)
- Connection technology 2-, 3-, 4-conductor
- Load/output load current output < 500 Ω (at 20 mA)
- Connection method Screw connection
- Screw thread M3
- Transmission error in the set measuring range ((100 K / set measurement range [K]) + 0.1)%
- Rated insulation voltage 50 V AC/DC
- Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
- Identification UL 508 Recognized
- Connection in acc. with standard CUL
- Vibration B
- ECLASS 5.1 27200200
- ECLASS 7.0 27200206
- ETIM 4.0 EC001446
- UNSPSC 13.2 41112105
- UNSPSC 20.0 41112105
- Electrical isolation Basic insulation according to EN 61010
- Noise emission EN 61000-6-4
- Humidity B
- ETIM 2.0 EC001446
- UNSPSC 7.0901 39121008
- UNSPSC 12.01 39121008
- Width 6.2 mm
- Degree of protection IP20
- Sensor types (RTD) that can be used Pt 100 (IEC 60751/EN 60751)
- Current output signal 0 mA ... 20 mA
- Max. output current 23 mA
- Max. output voltage approx. 12.5 V
- Degree of pollution 2
- Test voltage, input/output/supply 1.5 kV (50 Hz, 1 min.)
- Housing material PBT
- Designation Shipbuilding approval
- Electromagnetic compatibility Conformance with EMC directive
- Assembly instructions The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
- Standards/regulations EN 61000-4-6
- Temperature B
- Enclosure Required protection according to the Rules shall be provided upon installation on board
- Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
- Typical deviation from the measuring range final value 10 %
- REACh SVHC Lead 7439-92-1
- ECLASS 10.0.1 27210129
- ECLASS 6.0 27200200
- ETIM 6.0 EC002919
- UNSPSC 11 39121008
- UNSPSC 21.0 41112105
- Conductor cross section AWG 26 ... 12
- Mounting position any
- Certificate DNV GL TAA00002R0
- EMC A
- ECLASS 11.0 27210129
- ECLASS 4.0 27200200
- ETIM 7.0 EC002919
- UNSPSC 6.01 30211506
- Transmission error in the full measuring range ≤ 0,2 %
- Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
- UNSPSC 18.0 41112105
- Nominal supply voltage 24 V DC
- China RoHS Environmentally Friendly Use Period = 50 years
- ECLASS 4.1 27200200
- ECLASS 5.0 27200200
- ETIM 3.0 EC001446
- UNSPSC 19.0 41112105
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Manufacturer warranty
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
Fast Shipping & Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Need more details?
Feel free to chat with us
Relevant products
What can I help you find today?