3969925 Phoenix Contact Terminal Blocks

3969925 on Power Resource International
Phoenix Contact

Part#:3969925

Manufacturer:Phoenix Contact

Category:Terminal Blocks

Product Lifecycle:Active

Get a quick Quote!

Test terminal strip, nom. voltage: 400 V AC/DC, connection method: Ring cable lug, number of connections: 18, number of positions: 9, width: 106 mm, height: 70.1 mm, color: gray, mounting type: Wall mounting

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Terminal Blocks that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 3969925 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Calorimetric heat release NFPA 130 (ASTM E 1354)
    27,5 MJ/kg
  • Max. AWG conductor cross section, flexible
    8
  • Tightening torque max
    1.8 Nm
  • Cable lug width, max.
    8 mm
  • ECLASS 6.0
    27141100
  • Number of positions
    9
  • Maximum power dissipation for nominal condition
    1.31 W
  • Shock duration
    18 ms
  • Test surge voltage
    5 kV
  • Nominal voltage UN
    400 V AC/DC
  • Potentials
    9
  • Result of tight fit on support
    Test passed
  • Requirement temperature-rise test
    Increase in temperature ≤ 45 K
  • Result of thermal test
    Test passed
  • Test frequency
    f1 = 5 Hz to f2 = 250 Hz
  • Max. cross section for cable lug connection
    10 mm²
  • Max. tightening torque of the mounting screw:
    1 Nm
  • Number of connections
    18
  • Flammability rating according to UL 94
    V0
  • Overvoltage category
    III
  • Shock protection test specification
    DIN EN 50274 (VDE 0660-514):2002-11
  • Permissible humidity (storage/transport)
    30 % ... 70 %
  • ECLASS 10.0.1
    27141126
  • ECLASS 5.1
    27141100
  • ECLASS 9.0
    27141126
  • UNSPSC 12.01
    39121410
  • UNSPSC 21.0
    39121410
  • Result of temperature-rise test
    Test passed
  • Color
    gray
  • Rated surge voltage
    4 kV
  • Open side panel
    No
  • Result of surge voltage test
    Test passed
  • Result of the test for mechanical stability of terminal points (5 x conductor connection)
    Test passed
  • Note
    Test with 4 mm² / 500 A / 1 s includes test with 4 mm² / 480 A / 1 s in accordance with IEC 60947-7-1:2009-04.
  • Test specification, oscillation, broadband noise
    DIN EN 50155 (VDE 0115-200):2008-03
  • Test spectrum
    Service life test category 2, bogie-mounted
  • Test specification, shock test
    DIN EN 50155 (VDE 0115-200):2008-03
  • Shock form
    Half-sine
  • Static insulating material application in cold
    -60 °C
  • Width
    106 mm
  • Number of levels
    1
  • Insulating material
    PA
  • Back of the hand protection
    guaranteed
  • Terminal block mounting
    0.8 Nm ... 1 Nm
  • Result of power-frequency withstand voltage test
    Test passed
  • Result of voltage-drop test
    Test passed
  • Conductor cross section short circuit testing
    4 mm²
  • Short-time current
    1250 A
  • Oscillation, broadband noise test result
    Test passed
  • Test duration per axis
    5 h
  • Maximum load current
    30 A (with 10 mm² conductor cross section)
  • Note regarding shock protection
    Back of hand protection without cable lug, as well as with insulated and uninsulated cable lugs with shrink sleeve with tightened clamping screw.
  • Setpoint
    5 N
  • Short circuit stability result
    Test passed
  • Proof of thermal characteristics (needle flame) effective duration
    30 s
  • Acceleration
    30g
  • ASD level
    6.12 (m/s2)2/Hz
  • Number of shocks per direction
    3
  • Specific optical density of smoke NFPA 130 (ASTM E 662)
    passed
  • Connection in acc. with standard
    IEC 60947-7-1
  • 2 conductors with same cross section, solid max.
    6 mm²
  • 2 conductors with same cross section, stranded min.
    0.5 mm²
  • Internal cylindrical gage
    A5
  • Operating temperature
    -60 °C ... 105 °C (max. short-term operating temperature 130°C)
  • ECLASS 4.1
    27141100
  • ECLASS 7.0
    27141126
  • Fire protection for rail vehicles (DIN EN 45545-2) R24
    HL 1 - HL 3
  • 2 conductors with same cross section, stranded max.
    6 mm²
  • ECLASS 11.0
    27141126
  • UNSPSC 6.01
    30211811
  • UNSPSC 19.0
    39121410
  • Nominal cross section
    6 mm²
  • Min. tightening torque of the mounting screw:
    0.8 Nm
  • REACh SVHC
    Lead 7439-92-1
  • ETIM 6.0
    EC000902
  • UNSPSC 18.0
    39121410
  • Insulating material group
    I
  • Ambient temperature (assembly)
    -5 °C ... 70 °C
  • ETIM 4.0
    EC000897
  • UNSPSC 7.0901
    39121410
  • UNSPSC 20.0
    39121410
  • Mounting type
    Wall mounting
  • Connection
    1 level
  • Cable lug connection according to standard
    DIN 46237:1970-07
  • Hole diameter, min.
    4.3 mm
  • UNSPSC 13.2
    39121410
  • Fire protection for rail vehicles (DIN EN 45545-2) R23
    HL 1 - HL 3
  • Stripping length
    12 mm
  • 2 conductors with same cross section, solid min.
    0.5 mm²
  • ECLASS 5.0
    27141100
  • ETIM 7.0
    EC000902
  • Surface flammability NFPA 130 (ASTM E 162)
    passed
  • Plate thickness
    1 mm ... 4 mm
  • Tightening torque, min
    1.5 Nm
  • Min. cross section for cable lug connection
    0.5 mm²
  • Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
    125 °C
  • Bolt diameter
    4.1 mm
  • ECLASS 4.0
    27141100
  • Test directions
    X-, Y- and Z-axis (pos. and neg.)
  • Power frequency withstand voltage setpoint
    1.89 kV
  • Relative insulation material temperature index (Elec., UL 746 B)
    130 °C
  • Length
    81 mm
  • Ambient temperature (actuation)
    -5 °C ... 70 °C
  • China RoHS
    Environmentally friendly use period: unlimited = EFUP-e
  • Conductor cross section flexible max.
    10 mm²
  • Shock test result
    Test passed
  • Height
    70.1 mm
  • Smoke gas toxicity NFPA 130 (SMP 800C)
    passed
  • Fire protection for rail vehicles (DIN EN 45545-2) R26
    HL 1 - HL 3
  • Pitch
    8.2 mm
  • Connection method
    Ring cable lug
  • Min. AWG conductor cross section, flexible
    24
  • UNSPSC 11
    39121410
  • Conductor cross section flexible min.
    0.5 mm²
  • Ambient temperature (storage/transport)
    -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
  • Fire protection for rail vehicles (DIN EN 45545-2) R22
    HL 1 - HL 3
  • Screw thread
    No 8 UNC

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.


Manufacturer warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

Fast Shipping & Delivery


Secure Payment Processing


Warranty


Responsive Customer Support


Need more details?

Feel free to chat with us