3075919 Phoenix Contact Terminal Blocks

3075919 on Power Resource International
Phoenix Contact

Part#:3075919

Manufacturer:Phoenix Contact

Category:Terminal Blocks

Product Lifecycle:Active

Get a quick Quote!

Feed-through terminal block with bolt connection method, cross section: 2.5 - 35 mm², AWG: 12 - 2, width 17 mm, color: gray

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Terminal Blocks that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 3075919 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • End cover width
    2.2 mm
  • Pitch
    17 mm
  • Connection
    1 level
  • AWG min
    14
  • Bolt diameter
    6 mm
  • Ambient temperature (actuation)
    -5 °C ... 70 °C
  • ECLASS 10.0.1
    27141120
  • ECLASS 5.1
    27141100
  • ETIM 3.0
    EC000897
  • UNSPSC 11
    39121410
  • UNSPSC 21.0
    39121410
  • Nominal cross section
    35 mm²
  • Rated surge voltage
    8 kV
  • Insulating material group
    I
  • Result of power-frequency withstand voltage test
    Test passed
  • Result of voltage-drop test
    Test passed
  • Short circuit stability result
    Test passed
  • Conductor cross section short circuit testing
    35 mm²
  • Test frequency
    f1 = 5 Hz to f2 = 150 Hz
  • Acceleration
    5g
  • Test specification, shock test
    DIN EN 50155 (VDE 0115-200):2008-03
  • Shock duration
    30 ms
  • Surface flammability NFPA 130 (ASTM E 162)
    passed
  • Smoke gas toxicity NFPA 130 (SMP 800C)
    passed
  • Width
    17 mm
  • Connection method
    Bolt connection
  • Min. cross section for cable lug connection
    2.5 mm²
  • Hole diameter, min.
    6.5 mm
  • Tightening torque max
    3.7 Nm
  • Permissible humidity (storage/transport)
    30 % ... 70 %
  • ECLASS 5.0
    27141100
  • ECLASS 9.0
    27141120
  • UNSPSC 6.01
    30211811
  • UNSPSC 18.0
    39121410
  • Number of connections
    2
  • Flammability rating according to UL 94
    V0
  • Maximum load current
    125 A (with 35 mm² conductor cross section)
  • Nominal voltage UN
    800 V
  • Result of tight fit on support
    Test passed
  • Short-time current
    4.2 kA
  • Proof of thermal characteristics (needle flame) effective duration
    30 s
  • Test directions
    X-, Y- and Z-axis (pos. and neg.)
  • Shock test result
    Test passed
  • Static insulating material application in cold
    -60 °C
  • Specific optical density of smoke NFPA 130 (ASTM E 662)
    passed
  • Fire protection for rail vehicles (DIN EN 45545-2) R26
    HL 1 - HL 3
  • Stripping length
    The stripping length depends on the specification provided by the cable lug manufacturer.
  • Cable lug width, max.
    11 mm
  • Tightening torque, min
    3.2 Nm
  • Ambient temperature (storage/transport)
    -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
  • ECLASS 4.0
    27141100
  • ECLASS 7.0
    27141120
  • ETIM 7.0
    EC000897
  • UNSPSC 12.01
    39121410
  • UNSPSC 19.0
    39121410
  • Potentials
    1
  • Insulating material
    PA
  • Overvoltage category
    III
  • Open side panel
    No
  • Result of the test for mechanical stability of terminal points (5 x conductor connection)
    Test passed
  • Setpoint
    10 N
  • Requirement temperature-rise test
    Increase in temperature ≤ 45 K
  • Oscillation, broadband noise test result
    Test passed
  • Test specification, oscillation, broadband noise
    DIN EN 50155 (VDE 0115-200):2008-03
  • ASD level
    1.857 (m/s2)2/Hz
  • Shock form
    Half-sine
  • Relative insulation material temperature index (Elec., UL 746 B)
    130 °C
  • Calorimetric heat release NFPA 130 (ASTM E 1354)
    28 MJ/kg
  • Fire protection for rail vehicles (DIN EN 45545-2) R23
    HL 1 - HL 3
  • Fire protection for rail vehicles (DIN EN 45545-2) R24
    HL 1 - HL 3
  • Length
    80.8 mm
  • Connection in acc. with standard
    CUL
  • Cable lug connection according to standard
    DIN 46237:1970-07
  • Operating temperature
    -60 °C ... 105 °C (max. short-term operating temperature 130°C)
  • China RoHS
    Environmentally friendly use period: unlimited = EFUP-e
  • ECLASS 4.1
    27141100
  • ETIM 4.0
    EC000897
  • UNSPSC 7.0901
    39121410
  • UNSPSC 20.0
    39121410
  • Number of levels
    1
  • Color
    gray
  • Degree of pollution
    3
  • Maximum power dissipation for nominal condition
    4.06 W
  • Nominal current IN
    125 A
  • Result of surge voltage test
    Test passed
  • Power frequency withstand voltage setpoint
    2 kV
  • Result of temperature-rise test
    Test passed
  • Result of thermal test
    Test passed
  • Test spectrum
    Service life test category 1, class B, body mounted
  • Test duration per axis
    5 h
  • Number of shocks per direction
    3
  • Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
    130 °C
  • Fire protection for rail vehicles (DIN EN 45545-2) R22
    HL 1 - HL 3
  • Height
    39.7 mm
  • Max. cross section for cable lug connection
    6 mm²
  • AWG max
    10
  • Screw thread
    M6
  • Ambient temperature (assembly)
    -5 °C ... 70 °C
  • ECLASS 11.0
    27141120
  • ECLASS 6.0
    27141100
  • ETIM 6.0
    EC000897
  • UNSPSC 13.2
    39121410

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.


Manufacturer warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

Fast Shipping & Delivery


Secure Payment Processing


Warranty


Responsive Customer Support


Need more details?

Feel free to chat with us

What can I help you find today?