Test terminal strip, nom. voltage: 400 V AC/DC, connection method: Push-in connection, number of connections: 18, number of positions: 9, cross section: 0.5 mm² - 10 mm², AWG: 20 - 8, width: 106.6 mm, height: 56.5 mm, color: gray, mounting type: Wall moun
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Terminal Blocks that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 3069832 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Potentials 9
- Test surge voltage 5 kV
- Nominal voltage UN 400 V AC/DC
- Note regarding shock protection When test disconnect plug is plugged in.
- Bending test rotation speed 10 rpm
- Tensile test result Test passed
- Requirement temperature-rise test Increase in temperature ≤ 45 K
- Flammability rating according to UL 94 V0
- Number of positions 9
- Nominal cross section 6 mm²
- Maximum power dissipation for nominal condition 1.31 W
- UNSPSC 18.0 39121410
- Insulating material PA
- Insulating material group I
- Operating temperature -60 °C ... 105 °C (max. short-term operating temperature 130°C)
- ECLASS 10.0.1 27141126
- ECLASS 5.0 27141100
- China RoHS Environmentally friendly use period: unlimited = EFUP-e
- ECLASS 9.0 27141126
- UNSPSC 13.2 39121410
- ETIM 7.0 EC000902
- Number of connections 18
- Rated surge voltage 4 kV
- Maximum load current 30 A (with 6 mm² conductor cross section)
- Back of the hand protection guaranteed
- Result of the test for mechanical stability of terminal points (5 x conductor connection) Test passed
- Permissible humidity (storage/transport) 30 % ... 70 %
- REACh SVHC Lead 7439-92-1
- ECLASS 6.0 27141100
- ECLASS 11.0 27141126
- ETIM 6.0 EC000902
- UNSPSC 19.0 39121410
- UNSPSC 21.0 39121410
- Proof of thermal characteristics (needle flame) effective duration 30 s
- Ambient temperature (actuation) -5 °C ... 70 °C
- ECLASS 5.1 27141100
- ECLASS 7.0 27141126
- ETIM 4.0 EC000897
- UNSPSC 20.0 39121410
- Short-time current 0.15 kA
- Ageing test for screwless modular terminal block temperature cycles 192
- ASD level 6.12 (m/s2)2/Hz
- Shock test result Test passed
- Result of flexion and pull-out test Test passed
- Setpoint 5 N
- Color gray
- Bending test turns 135
- Conductor cross section short circuit testing 4 mm²
- Test spectrum Service life test category 2, bogie-mounted
- Test duration per axis 5 h
- Pitch 8.2 mm
- Result of tight fit on support Test passed
- Short circuit stability result Test passed
- Test directions X-, Y- and Z-axis (pos. and neg.)
- Shock form Half-sine
- Number of levels 1
- Static insulating material application in cold -60 °C
- Overvoltage category III
- Open side panel No
- Finger protection guaranteed
- Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
- Smoke gas toxicity NFPA 130 (SMP 800C) passed
- Length 81 mm
- Conductor cross section solid min. 1 mm²
- Acceleration 30g
- Number of shocks per direction 3
- Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
- Plate thickness 1 mm ... 4 mm
- Conductor cross section flexible min. 0.5 mm²
- Shock protection test specification DIN EN 50274 (VDE 0660-514):2002-11
- Result of power-frequency withstand voltage test Test passed
- Result of surge voltage test Test passed
- Bending test conductor cross section/weight 0.5 mm² / 0.3 kg
- Result of temperature-rise test Test passed
- Result of aging test Test passed
- Oscillation, broadband noise test result Test passed
- Terminal block mounting 0.8 Nm ... 1 Nm
- Power frequency withstand voltage setpoint 1.89 kV
- Note The measuring transducer block is replaced every 100 cycles.
- Result of voltage-drop test Test passed
- Result of thermal test Test passed
- Test specification, oscillation, broadband noise DIN EN 50155 (VDE 0115-200):2008-03
- Conductor cross section flexible, with ferrule with plastic sleeve min. 1 mm²
- Max. tightening torque of the mounting screw: 1 Nm
- Conductor cross section AWG max. 8
- Max. AWG conductor cross section, flexible 10
- Conductor cross section flexible, with ferrule without plastic sleeve min. 1 mm²
- Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum 0.5 mm²
- Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum 1.5 mm²
- Stripping length 12 mm
- Conductor cross section flexible, with ferrule without plastic sleeve max. 6 mm²
- Connection cross sections directly pluggable 1 mm² 10 mm²
- Mounting type Wall mounting
- Test specification, shock test DIN EN 50155 (VDE 0115-200):2008-03
- Specific optical density of smoke NFPA 130 (ASTM E 662) passed
- Connection in acc. with standard IEC 60947-7-1
- Conductor cross section flexible max. 6 mm²
- Conductor cross section flexible, with ferrule with plastic sleeve max. 6 mm²
- Min. tightening torque of the mounting screw: 0.8 Nm
- Ambient temperature (assembly) -5 °C ... 70 °C
- Test frequency f1 = 5 Hz to f2 = 250 Hz
- Shock duration 18 ms
- Relative insulation material temperature index (Elec., UL 746 B) 130 °C
- Surface flammability NFPA 130 (ASTM E 162) passed
- Width 106.6 mm
- Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3
- Connection 1 level
- Connection method Push-in connection
- Conductor cross section AWG min. 20
- Ambient temperature (storage/transport) -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
- Calorimetric heat release NFPA 130 (ASTM E 1354) 27,5 MJ/kg
- Conductor cross section solid max. 10 mm²
- Min. AWG conductor cross section, flexible 20
- Internal cylindrical gage A5
- Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) 125 °C
- Height 56.5 mm
- Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Manufacturer warranty