3069827 Phoenix Contact Terminal Blocks

3069827 on Power Resource International
Phoenix Contact

Part#:3069827

Manufacturer:Phoenix Contact

Category:Terminal Blocks

Product Lifecycle:Active

Get a quick Quote!

Test terminal strip, nom. voltage: 400 V AC/DC, connection method: Push-in connection, number of connections: 8, number of positions: 4, cross section: 0.5 mm² - 10 mm², AWG: 20 - 8, width: 65.6 mm, height: 56.5 mm, color: gray, mounting type: Wall mounti

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Terminal Blocks that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 3069827 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Number of levels
    1
  • Maximum load current
    30 A (with 6 mm² conductor cross section)
  • Shock protection test specification
    DIN EN 50274 (VDE 0660-514):2002-11
  • Requirement temperature-rise test
    Increase in temperature ≤ 45 K
  • Oscillation, broadband noise test result
    Test passed
  • Test spectrum
    Service life test category 2, bogie-mounted
  • Acceleration
    30g
  • Test specification, shock test
    DIN EN 50155 (VDE 0115-200):2008-03
  • Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
    125 °C
  • Surface flammability NFPA 130 (ASTM E 162)
    passed
  • Fire protection for rail vehicles (DIN EN 45545-2) R24
    HL 1 - HL 3
  • Height
    56.5 mm
  • Stripping length
    12 mm
  • Connection method
    Push-in connection
  • Conductor cross section flexible min.
    0.5 mm²
  • Mounting type
    Wall mounting
  • Number of positions
    4
  • Nominal cross section
    6 mm²
  • Number of connections
    8
  • Maximum power dissipation for nominal condition
    1.31 W
  • Nominal voltage UN
    400 V AC/DC
  • Open side panel
    No
  • Note regarding shock protection
    When test disconnect plug is plugged in.
  • Result of the test for mechanical stability of terminal points (5 x conductor connection)
    Test passed
  • Result of flexion and pull-out test
    Test passed
  • Note
    The measuring transducer block is replaced every 100 cycles.
  • Setpoint
    5 N
  • Conductor cross section short circuit testing
    4 mm²
  • Proof of thermal characteristics (needle flame) effective duration
    30 s
  • Test frequency
    f1 = 5 Hz to f2 = 250 Hz
  • Shock test result
    Test passed
  • Test duration per axis
    5 h
  • Potentials
    4
  • Flammability rating according to UL 94
    V0
  • Rated surge voltage
    4 kV
  • Color
    gray
  • Terminal block mounting
    0.8 Nm ... 1 Nm
  • Shock form
    Half-sine
  • Shock duration
    18 ms
  • Calorimetric heat release NFPA 130 (ASTM E 1354)
    27,5 MJ/kg
  • Smoke gas toxicity NFPA 130 (SMP 800C)
    passed
  • ECLASS 10.0.1
    27141126
  • ECLASS 5.0
    27141100
  • ETIM 6.0
    EC000902
  • Insulating material group
    I
  • Operating temperature
    -60 °C ... 105 °C (max. short-term operating temperature 130°C)
  • Min. tightening torque of the mounting screw:
    0.8 Nm
  • Overvoltage category
    III
  • Back of the hand protection
    guaranteed
  • Tensile test result
    Test passed
  • Short-time current
    0.15 kA
  • Number of shocks per direction
    3
  • Insulating material
    PA
  • Power frequency withstand voltage setpoint
    1.89 kV
  • Bending test turns
    135
  • Result of tight fit on support
    Test passed
  • Result of temperature-rise test
    Test passed
  • Test specification, oscillation, broadband noise
    DIN EN 50155 (VDE 0115-200):2008-03
  • Height NS 35/7,5
    58.5 mm
  • Pitch
    8.2 mm
  • Connection
    1 level
  • Internal cylindrical gage
    A5
  • Result of power-frequency withstand voltage test
    Test passed
  • Bending test conductor cross section/weight
    0.5 mm² / 0.3 kg
  • Short circuit stability result
    Test passed
  • Ageing test for screwless modular terminal block temperature cycles
    192
  • Result of aging test
    Test passed
  • Length
    81 mm
  • Max. tightening torque of the mounting screw:
    1 Nm
  • Ambient temperature (assembly)
    -5 °C ... 70 °C
  • China RoHS
    Environmentally friendly use period: unlimited = EFUP-e
  • ECLASS 11.0
    27141126
  • ECLASS 7.0
    27141126
  • ETIM 7.0
    EC000902
  • Test surge voltage
    5 kV
  • Result of surge voltage test
    Test passed
  • Finger protection
    guaranteed
  • Bending test rotation speed
    10 rpm
  • Result of voltage-drop test
    Test passed
  • Result of thermal test
    Test passed
  • Fire protection for rail vehicles (DIN EN 45545-2) R23
    HL 1 - HL 3
  • Plate thickness
    1 mm ... 4 mm
  • Conductor cross section flexible, with ferrule without plastic sleeve min.
    1 mm²
  • Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum
    1.5 mm²
  • Ambient temperature (storage/transport)
    -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
  • Ambient temperature (actuation)
    -5 °C ... 70 °C
  • ECLASS 9.0
    27141126
  • UNSPSC 18.0
    39121410
  • Permissible humidity (storage/transport)
    30 % ... 70 %
  • ECLASS 5.1
    27141100
  • UNSPSC 13.2
    39121410
  • UNSPSC 20.0
    39121410
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 6.0
    27141100
  • ETIM 4.0
    EC000897
  • UNSPSC 21.0
    39121410
  • UNSPSC 19.0
    39121410
  • Width
    65.6 mm
  • Fire protection for rail vehicles (DIN EN 45545-2) R26
    HL 1 - HL 3
  • Conductor cross section solid max.
    10 mm²
  • Min. AWG conductor cross section, flexible
    20
  • Conductor cross section flexible, with ferrule with plastic sleeve min.
    1 mm²
  • Fire protection for rail vehicles (DIN EN 45545-2) R22
    HL 1 - HL 3
  • Connection in acc. with standard
    IEC 60947-7-1
  • Conductor cross section flexible, with ferrule without plastic sleeve max.
    6 mm²
  • Connection cross sections directly pluggable
    1 mm² 10 mm²
  • ASD level
    6.12 (m/s2)2/Hz
  • Test directions
    X-, Y- and Z-axis (pos. and neg.)
  • Max. AWG conductor cross section, flexible
    10
  • Conductor cross section AWG max.
    8
  • Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum
    0.5 mm²
  • Conductor cross section solid min.
    1 mm²
  • Conductor cross section flexible, with ferrule with plastic sleeve max.
    6 mm²
  • Relative insulation material temperature index (Elec., UL 746 B)
    130 °C
  • Static insulating material application in cold
    -60 °C
  • Specific optical density of smoke NFPA 130 (ASTM E 662)
    passed
  • Conductor cross section AWG min.
    20
  • Conductor cross section flexible max.
    6 mm²

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.


Manufacturer warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

Fast Shipping & Delivery


Secure Payment Processing


Warranty


Responsive Customer Support


Need more details?

Feel free to chat with us

What can I help you find today?