Test terminal strip, nom. voltage: 400 V AC/DC, connection method: Screw connection, number of connections: 16, number of positions: 8, cross section: 0.2 mm² - 10 mm², AWG: 24 - 8, width: 97.8 mm, height: 56.5 mm, color: gray, mounting type: Wall mountin

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Terminal Blocks that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 3069655 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Number of levels
    1
  • Insulating material
    PA
  • Setpoint
    5 N
  • Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum
    0.25 mm²
  • Mounting type
    Wall mounting
  • Operating temperature
    -60 °C ... 105 °C (max. short-term operating temperature 130°C)
  • Ambient temperature (actuation)
    -5 °C ... 70 °C
  • ECLASS 4.1
    27141100
  • ECLASS 9.0
    27141148
  • UNSPSC 7.0901
    39121410
  • Result of power-frequency withstand voltage test
    Test passed
  • Number of connections
    16
  • Color
    gray
  • Overvoltage category
    III
  • Maximum power dissipation for nominal condition
    1.31 W
  • Nominal voltage UN
    400 V AC/DC
  • Result of the test for mechanical stability of terminal points (5 x conductor connection)
    Test passed
  • Bending test conductor cross section/weight
    0.2 mm² / 0.2 kg
  • Tensile test result
    Test passed
  • Note
    25 pos.
  • Pitch
    8.2 mm
  • UNSPSC 6.01
    30211811
  • Ambient temperature (assembly)
    -5 °C ... 70 °C
  • Min. AWG conductor cross section, flexible
    24
  • Conductor cross section flexible, with ferrule with plastic sleeve min.
    0.25 mm²
  • 2 conductors with same cross section, solid min.
    0.2 mm²
  • Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum
    2.5 mm²
  • Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum
    1.5 mm²
  • Permissible humidity (storage/transport)
    30 % ... 70 %
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 4.0
    27141100
  • ECLASS 7.0
    27141148
  • Internal cylindrical gage
    A5
  • Ambient temperature (storage/transport)
    -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
  • ECLASS 10.0.1
    27141148
  • UNSPSC 18.0
    20122006
  • UNSPSC 20.0
    20122006
  • Relative insulation material temperature index (Elec., UL 746 B)
    130 °C
  • Calorimetric heat release NFPA 130 (ASTM E 1354)
    27,5 MJ/kg
  • Result of surge voltage test
    Test passed
  • Bending test rotation speed
    10 rpm
  • Result of temperature-rise test
    Test passed
  • Short-time current
    500 A
  • Ageing test for screwless modular terminal block temperature cycles
    192
  • Flammability rating according to UL 94
    V0
  • Insulating material group
    I
  • Acceleration
    30g
  • Fire protection for rail vehicles (DIN EN 45545-2) R26
    HL 1 - HL 3
  • Connection
    1 level
  • Tightening torque max
    1.8 Nm
  • Result of aging test
    Test passed
  • Power frequency withstand voltage setpoint
    1.89 kV
  • Result of voltage-drop test
    Test passed
  • Short circuit stability result
    Test passed
  • Test frequency
    f1 = 5 Hz to f2 = 250 Hz
  • Test duration per axis
    5 h
  • Shock form
    Half-sine
  • Static insulating material application in cold
    -60 °C
  • Fire protection for rail vehicles (DIN EN 45545-2) R23
    HL 1 - HL 3
  • Height
    56.5 mm
  • Potentials
    8
  • Maximum load current
    30 A (with 10 mm² conductor cross section)
  • Requirement temperature-rise test
    Increase in temperature ≤ 45 K
  • Result of thermal test
    Test passed
  • Test specification, oscillation, broadband noise
    DIN EN 50155 (VDE 0115-200):2008-03
  • ASD level
    6.12 (m/s2)2/Hz
  • Shock test result
    Test passed
  • Specific optical density of smoke NFPA 130 (ASTM E 662)
    passed
  • Fire protection for rail vehicles (DIN EN 45545-2) R24
    HL 1 - HL 3
  • Screw thread
    M4
  • Tightening torque, min
    1.5 Nm
  • Number of positions
    8
  • Nominal cross section
    6 mm²
  • Test surge voltage
    5 kV
  • Bending test turns
    135
  • Proof of thermal characteristics (needle flame) effective duration
    30 s
  • Test spectrum
    Service life test category 2, bogie-mounted
  • Test directions
    X-, Y- and Z-axis (pos. and neg.)
  • Shock duration
    18 ms
  • Surface flammability NFPA 130 (ASTM E 162)
    passed
  • Rated surge voltage
    4 kV
  • Open side panel
    No
  • Result of flexion and pull-out test
    Test passed
  • Result of tight fit on support
    Test passed
  • Conductor cross section short circuit testing
    4 mm²
  • Oscillation, broadband noise test result
    Test passed
  • Test specification, shock test
    DIN EN 50155 (VDE 0115-200):2008-03
  • Conductor cross section flexible, with ferrule without plastic sleeve min.
    0.25 mm²
  • 2 conductors with same cross section, stranded min.
    0.2 mm²
  • ECLASS 5.0
    27141100
  • ETIM 7.0
    EC002555
  • UNSPSC 11
    39121410
  • UNSPSC 21.0
    20122006
  • Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
    125 °C
  • Length
    81 mm
  • Conductor cross section AWG max.
    8
  • Conductor cross section flexible max.
    10 mm²
  • ECLASS 6.0
    27141100
  • UNSPSC 12.01
    39121410
  • 2 conductors with same cross section, stranded max.
    2.5 mm²
  • Fire protection for rail vehicles (DIN EN 45545-2) R22
    HL 1 - HL 3
  • Width
    97.8 mm
  • Stripping length
    12 mm
  • Conductor cross section flexible min.
    0.2 mm²
  • Conductor cross section flexible, with ferrule without plastic sleeve max.
    6 mm²
  • Conductor cross section solid max.
    10 mm²
  • Conductor cross section AWG min.
    24
  • Conductor cross section flexible, with ferrule with plastic sleeve max.
    6 mm²
  • UNSPSC 19.0
    20122006
  • Number of shocks per direction
    3
  • Smoke gas toxicity NFPA 130 (SMP 800C)
    passed
  • Connection in acc. with standard
    IEC 60947-7-1
  • ECLASS 5.1
    27141100
  • Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum
    0.5 mm²
  • Max. AWG conductor cross section, flexible
    8
  • ETIM 6.0
    EC002555
  • ETIM 4.0
    EC000901
  • UNSPSC 13.2
    20122006
  • Connection method
    Screw connection
  • Conductor cross section solid min.
    0.2 mm²
  • 2 conductors with same cross section, solid max.
    2.5 mm²
  • ECLASS 11.0
    27141148

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.


Manufacturer warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

Fast Shipping & Delivery


Secure Payment Processing


Warranty


Responsive Customer Support


Need more details?

Feel free to chat with us

What can I help you find today?