Motor terminal block, four-level, connection method: spring-cage connection, cross section: 0.08 mm² - 6 mm², AWG: 28 - 10, width: 6.2 mm, color: gray, mounting type: NS 35/7,5, NS 35/15

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Terminal Blocks that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 3038338 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Color
    gray
  • Connection in acc. with standard
    CSA
  • Conductor cross section AWG min.
    28
  • Conductor cross section AWG max.
    10
  • Conductor cross section flexible, with ferrule without plastic sleeve max.
    4 mm²
  • Connection
    1st, 2nd, 3rd and 4th level
  • Max. AWG conductor cross section, flexible
    12
  • Conductor cross section flexible, with ferrule with plastic sleeve min.
    0.14 mm²
  • Ambient temperature (assembly)
    -5 °C ... 70 °C
  • ECLASS 5.0
    27141100
  • UNSPSC 7.0901
    39121410
  • UNSPSC 18.0
    39121410
  • UNSPSC 21.0
    39121410
  • Connection method
    Spring-cage connection
  • Conductor cross section solid min.
    0.08 mm²
  • Conductor cross section flexible min.
    0.08 mm²
  • Conductor cross section flexible, with ferrule with plastic sleeve max.
    4 mm²
  • Internal cylindrical gage
    A4
  • China RoHS
    Environmentally friendly use period: unlimited = EFUP-e
  • ECLASS 4.1
    27141100
  • Conductor cross section flexible max.
    4 mm²
  • Conductor cross section flexible, with ferrule without plastic sleeve min.
    0.14 mm²
  • ECLASS 10.0.1
    27141120
  • Ambient temperature (actuation)
    -5 °C ... 70 °C
  • ECLASS 6.0
    27141100
  • ETIM 3.0
    EC000897
  • Min. AWG conductor cross section, flexible
    28
  • Operating temperature
    -60 °C ... 105 °C (max. short-term operating temperature 130°C)
  • Ambient temperature (storage/transport)
    -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
  • ECLASS 11.0
    27141120
  • ECLASS 4.0
    27141100
  • ECLASS 7.0
    27141120
  • ECLASS 5.1
    27141100
  • Surface flammability NFPA 130 (ASTM E 162)
    passed
  • Number of levels
    4
  • Potentials
    4
  • Rated surge voltage
    8 kV
  • Open side panel
    No
  • Back of the hand protection
    guaranteed
  • Result of surge voltage test
    Test passed
  • Result of tight fit on support
    Test passed
  • Result of temperature-rise test
    Test passed
  • Result of thermal test
    Test passed
  • Permissible humidity (storage/transport)
    30 % ... 70 %
  • ETIM 4.0
    EC000897
  • UNSPSC 19.0
    39121410
  • Maximum power dissipation for nominal condition
    1.02 W (the value is multiplied when connecting multiple levels)
  • Nominal current IN
    28 A (with 6 mm² conductor cross section)
  • Power frequency withstand voltage setpoint
    2 kV
  • Result of flexion and pull-out test
    Test passed
  • Bending test turns
    135
  • Requirement temperature-rise test
    Increase in temperature ≤ 45 K
  • Ageing test for screwless modular terminal block temperature cycles
    192
  • ASD level
    6.12 (m/s2)2/Hz
  • Test duration per axis
    5 h
  • Test specification, shock test
    DIN EN 50155 (VDE 0115-200):2008-03
  • Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
    130 °C
  • Smoke gas toxicity NFPA 130 (SMP 800C)
    passed
  • Fire protection for rail vehicles (DIN EN 45545-2) R26
    HL 1 - HL 3
  • Height NS 35/7,5
    83.5 mm
  • Stripping length
    8 mm ... 10 mm
  • Conductor cross section solid max.
    6 mm²
  • ECLASS 9.0
    27141120
  • ETIM 7.0
    EC000897
  • UNSPSC 11
    39121410
  • Number of connections
    7
  • Degree of pollution
    3
  • Nominal voltage UN
    800 V
  • Result of power-frequency withstand voltage test
    Test passed
  • Bending test rotation speed
    10 rpm
  • Setpoint
    1 N
  • Short circuit stability result
    Test passed
  • Result of aging test
    Test passed
  • Test specification, oscillation, broadband noise
    DIN EN 50155 (VDE 0115-200):2008-03
  • Shock duration
    18 ms
  • Number of shocks per direction
    3
  • Fire protection for rail vehicles (DIN EN 45545-2) R23
    HL 1 - HL 3
  • Fire protection for rail vehicles (DIN EN 45545-2) R22
    HL 1 - HL 3
  • Height NS 35/15
    91 mm
  • UNSPSC 12.01
    39121410
  • UNSPSC 20.0
    39121410
  • Insulating material
    PA
  • Overvoltage category
    III
  • Maximum load current
    32 A (with 6 mm² conductor cross section)
  • Shock protection test specification
    DIN EN 50274 (VDE 0660-514):2002-11
  • Bending test conductor cross section/weight
    0.08 mm² / 0.1 kg
  • Tight fit on carrier
    NS 35
  • Conductor cross section short circuit testing
    6 mm²
  • Proof of thermal characteristics (needle flame) effective duration
    30 s
  • Test frequency
    f1 = 5 Hz to f2 = 250 Hz
  • Test directions
    X-, Y- and Z-axis (pos. and neg.)
  • Shock form
    Half-sine
  • Calorimetric heat release NFPA 130 (ASTM E 1354)
    28 MJ/kg
  • Specific optical density of smoke NFPA 130 (ASTM E 662)
    passed
  • Length
    101 mm
  • Width
    6.2 mm
  • Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum
    1 mm²
  • ETIM 2.0
    EC000897
  • UNSPSC 13.2
    39121410
  • Nominal cross section
    4 mm²
  • Flammability rating according to UL 94
    V0
  • Insulating material group
    I
  • Finger protection
    guaranteed
  • Result of the test for mechanical stability of terminal points (5 x conductor connection)
    Test passed
  • Tensile test result
    Test passed
  • Result of voltage-drop test
    Test passed
  • Short-time current
    0.72 kA
  • Oscillation, broadband noise test result
    Test passed
  • Test spectrum
    Service life test category 2, bogie-mounted
  • Acceleration
    30g
  • Shock test result
    Test passed
  • Relative insulation material temperature index (Elec., UL 746 B)
    130 °C
  • Static insulating material application in cold
    -60 °C
  • Fire protection for rail vehicles (DIN EN 45545-2) R24
    HL 1 - HL 3
  • Note
    Please observe the current carrying capacity of the DIN rails.
  • Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum
    0.5 mm²
  • ETIM 6.0
    EC000897
  • UNSPSC 6.01
    30211811

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.


Manufacturer warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

Fast Shipping & Delivery


Secure Payment Processing


Warranty


Responsive Customer Support


Need more details?

Feel free to chat with us

What can I help you find today?