2963802 Phoenix Contact Electrical Safety Devices

2963802 on Power Resource International
Phoenix Contact

Part#:2963802

Manufacturer:Phoenix Contact

Category:Electrical Safety Devices

Product Lifecycle:Active

Get a quick Quote!

Safety relay for emergency stop and safety door up to SIL 1, SIL CL 1, Cat. 1, PL c, depending on the application up to SIL 3, SIL CL 3, Cat. 4, PL e, single-channel operation, 4 enabling current paths, US =  24 V AC/DC, plug-in screw terminal blocks

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Safety Devices that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2963802 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Max. permissible relative humidity (operation)
    75 % (on average, 85% infrequently, non-condensing)
  • Power consumption at US
    typ. 3.36 W (AC)
  • Typical release time
    < 45 ms (when controlled via S12)
  • Recovery time
    < 1 s
  • Filter time
    2 ms (at A1 in the event of voltage dips at Us)
  • Sq. Total current
    72 A2 (observe derating)
  • Mechanical service life
    10x 106 cycles
  • Relay type
    Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
  • Degree of protection
    IP20
  • Conductor cross section solid
    0.2 mm² ... 2.5 mm²
  • Stop category
    0
  • Category
    1 (up to Cat. 4 depending on the application)
  • Rated insulation voltage
    250 V AC
  • ECLASS 11.0
    27371819
  • ETIM 2.0
    EC000196
  • ETIM 7.0
    EC001449
  • UNSPSC 12.01
    39121501
  • UNSPSC 20.0
    39122205
  • Utilization restriction
    EMC: class A product, see manufacturer's declaration in the download area
  • Depth
    114.5 mm
  • Ambient temperature (operation)
    -20 °C ... 65 °C (observe derating)
  • Maximum altitude
    ≤ 2000 m (Above sea level)
  • Voltage at input/start and feedback circuit
    24 V DC -15 % / +10 %
  • Typical response time
    < 65 ms (automatic start)
  • Protective circuit
    Surge protection Suppressor diode
  • Contact material
    AgSnO2
  • Width
    22.5 mm
  • Max. permissible humidity (storage/transport)
    75 % (on average, 85% infrequently, non-condensing)
  • Rated control circuit supply voltage US
    24 V AC/DC -15 % / +10 %
  • Inrush current
    2 A (Δt = 10 ms at Us)
  • Operating voltage display
    1 x green LED
  • Maximum switching frequency
    1 Hz
  • Maximum inrush current
    20 A (Δt  100 ms)
  • Output fuse
    10 A gL/gG (N/O contact)
  • Mounting position
    vertical or horizontal
  • Housing color
    yellow
  • Min. degree of protection of inst. location
    IP54
  • pluggable
    Yes
  • Safety Integrity Level (SIL)
    1 (up to SIL 3 depending on the application)
  • Degree of pollution
    2
  • Conformance
    CE-compliant
  • ECLASS 5.0
    27371900
  • ECLASS 6.0
    27371800
  • ETIM 3.0
    EC001449
  • UNSPSC 19.0
    39122205
  • Ambient temperature (storage/transport)
    -40 °C ... 70 °C
  • Current consumption
    < 50 mA (with Us/Ix to S12)
  • Status display
    2 x green LEDs
  • Maximum switching voltage
    250 V AC/DC (Observe the load curve)
  • Inrush current, minimum
    10 mA
  • Interrupting rating (ohmic load) max.
    144 W (24 V DC, τ = 0 ms)
  • ECLASS 10.0.1
    27371819
  • ECLASS 9.0
    27371819
  • ETIM 6.0
    EC001449
  • UNSPSC 6.01
    30211901
  • UNSPSC 21.0
    39122205
  • Height
    99 mm
  • Rated control supply current IS
    typ. 140 mA AC
  • Typ. starting time with Us
    < 65 ms (when controlled via A1)
  • Max. permissible overall conductor resistance
    approx. 22 Ω (Input and start circuits at US)
  • Contact type
    4 enabling current paths
  • Limiting continuous current
    6 A (N/O contact, pay attention to the derating)
  • Switching capacity min.
    50 mW
  • Nominal operating mode
    100% operating factor
  • Mounting type
    DIN rail mounting
  • Housing material
    PBT
  • Conductor cross-section AWG
    24 ... 12
  • Stripping length
    7 mm
  • Performance level (PL)
    c (up to PL e depending on the application)
  • Rated surge voltage/insulation
    Basic insulation 4 kV:between all current paths and housingSafe isolation, reinforced insulation 6 kV:between A1/A2 and 13/14, 23/24, 33/34, 43/44between S11/S12/S33/S34 and 13/14, 23/24, 33/34, 43/44between 51/52 and 13/14, 23/24, 33/34, 43/44
  • Shock
    15g
  • Overvoltage category
    III
  • ECLASS 4.0
    40020600
  • ECLASS 5.1
    27371900
  • ECLASS 7.0
    27371819
  • UNSPSC 11
    39121501
  • UNSPSC 13.2
    39121501
  • Minimum switching voltage
    5 V AC/DC
  • Maximum interrupting rating (inductive load)
    42 W (24 V DC, τ = 40 ms)
  • Switching capacity (360/h cycles)
    4 A (24 V DC)
  • Net weight
    210.5 g
  • Assembly instructions
    See derating curve
  • Connection method
    Screw connection
  • Conductor cross section flexible
    0.2 mm² ... 2.5 mm²
  • Screw thread
    M3
  • Designation
    Air clearances and creepage distances between the power circuits
  • Safety Integrity Level Claim Limit (SIL CL)
    1 (up to SILCL 3 depending on the application)
  • Standards/regulations
    DIN EN 50178/VDE 0160
  • Vibration (operation)
    10 Hz ... 150 Hz, 2g
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 4.1
    40020600
  • ETIM 4.0
    EC001449
  • UNSPSC 7.0901
    39121501
  • UNSPSC 18.0
    39122205

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.


Manufacturer warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

Fast Shipping & Delivery


Secure Payment Processing


Warranty


Responsive Customer Support


Need more details?

Feel free to chat with us

What can I help you find today?