2924252 Phoenix Contact Electrical Measuring & Monitoring Instruments
Part#:2924252
Manufacturer:Phoenix Contact
Category:Electrical Measuring & Monitoring Instruments
Product Lifecycle:Active
Get a quick Quote!
NAMUR signal conditioner for operating proximity sensors and switches. The signals are transmitted to the control level via relay output (changeover contact). Line fault detection (LFD), 3-way electrical isolation, SIL 2, with Push-in connection.
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2924252 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Ambient temperature (operation) -20 °C ... 60 °C (Any mounting position)
- Width 12.5 mm
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Degree of protection IP20 (not assessed by UL)
- Line fault detection Break 0.05 mA < IIN < 0.35 mA
- Maximum switching voltage 250 V AC (2 A)
- Depth 114.5 mm
- Permissible humidity (operation) 10 % ... 95 % (non-condensing)
- Short-circuit current ~ 8 mA
- Contact material AgSnO2, hard gold-plated
- Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
- Maximum altitude ≤ 2000 m
- Switching points (attenuated) < 1.2 mA (blocking)
- Noise immunity EN 61000-6-2 EN 61326
- Available input sources NAMUR proximity sensors (EN 60947-5-6)
- Maximum switching capacity 500 VA
- Supply voltage range 19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
- Conductor cross section AWG 24 ... 16
- Switching frequency ≤ 20 Hz (without load)
- Conductor cross section flexible 0.2 mm² ... 1.5 mm²
- No. of channels 1
- Electromagnetic compatibility Conformance with EMC directive
- Color gray
- Test voltage 2.5 kV AC (50 Hz, 1 min.)
- Power dissipation < 650 mW
- Connection method Push-in connection
- Stripping length 8 mm
- Switching output Relay output
- Mechanical service life 107 cycles
- Max. current consumption 21 mA (24 V DC)
- ECLASS 7.0 27210121
- Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
- Contact type 1 changeover contact
- Nominal supply voltage 24 V DC
- Status display Green LED (supply voltage)
- Insulation Safe isolation in accordance with IEC/EN 61010-1
- Safety Integrity Level (SIL) 2
- λSD 1 x 10-9 (1 FIT)
- Probability of a hazardous failure on demand (PFDAVG) 3.01 x 10-4 (1 year)
- UL, USA/Canada UL 508 Listed
- DNV GL-Humidity B
- Humidity B
- Vibration A
- REACh SVHC Lead 7439-92-1
- ECLASS 5.0 27210100
- ECLASS 5.1 27210100
- UNSPSC 6.01 30211506
- UNSPSC 11 39121008
- UNSPSC 20.0 39121008
- Height 116 mm
- Switching hysteresis < 0.2 mA
- Housing material PA 6.6-FR
- Designation Safety Integrity Level (SIL, IEC 61508)
- Degree of pollution 2
- Safe Failure Fraction (SFF) 78 %
- λDD 6 x 10-9 (6 FIT)
- Diagnostic coverage (DC) DCS = 0.4 %, DCD = 8 %
- Noise emission EN 61000-6-4
- DNV GL-EMC B
- Identification 2
- China RoHS Environmentally Friendly Use Period = 50 years
- ECLASS 4.1 27210100
- ECLASS 6.0 27210100
- ETIM 2.0 EC001485
- ETIM 7.0 EC001485
- UNSPSC 12.01 39121008
- UNSPSC 21.0 39121008
- Switching points (unattenuated) > 2.1 mA (conductive)
- Conductor cross section solid 0.2 mm² ... 1.5 mm²
- Overvoltage category II
- Rated insulation voltage 300 Vrms
- Equipment type Type A
- λDU 6.2 x 10-8 (62 FIT)
- ATEX II 3 G Ex nA nC IIC T4 Gc X
- DNV GL-Vibration A
- Additional text and EN 61326-1
- Certificate DNV GL TAA00000AG
- EMC B
- ECLASS 10.0.1 27210121
- ETIM 3.0 EC001485
- ETIM 6.0 EC001485
- UNSPSC 13.2 39121008
- UNSPSC 19.0 39121008
- Non-load voltage ~ 8 V DC
- Power consumption < 650 mW
- Interference emission EN 61000-6-4
- Electrical isolation 375 V (Peak value in accordance with IEC/EN 60079-11)
- Integrity requirement IEC 61508 - Low demand
- λSU 2.48 x 10-7 (248 FIT)
- Conformance CE-compliant, additionally EN 61326-1
- DNV GL-Temperature B
- DNV GL-Enclosure Required protection according to the Rules shall be provided upon installation on board
- Temperature B
- Enclosure Required protection according to the Rules shall be provided upon installation on board
- ECLASS 11.0 27210121
- ECLASS 4.0 27210100
- ECLASS 9.0 27210121
- ETIM 4.0 EC001485
- UNSPSC 7.0901 39121008
- UNSPSC 18.0 39121008
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Manufacturer warranty
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
Fast Shipping & Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Need more details?
Feel free to chat with us
What can I help you find today?