2924236 Phoenix Contact Electrical Measuring & Monitoring Instruments

2924236 on Power Resource International
Phoenix Contact

Part#:2924236

Manufacturer:Phoenix Contact

Category:Electrical Measuring & Monitoring Instruments

Product Lifecycle:Active

Get a quick Quote!

Ex i measuring transducer power supply and input signal conditioner, HART-transparent. Transfers supplied or active 0/4…20 mA electrical isolation signals from the Ex area to two loads in the safe area. 4-way electrical isolation, Push-in connection, SIL,

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2924236 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Height
    116 mm
  • Ambient temperature (storage/transport)
    -40 °C ... 80 °C
  • Noise immunity
    EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
  • Output behavior in the event of an error
    0 mA (Cable break in the input)
  • Connection method
    Push-in connection
  • Rated insulation voltage
    300 Vrms
  • Protocols supported
    HART
  • Signal input
    Signal conditioner operation
  • Polarization and surge protection
    Yes
  • Output ripple
    < 20 mVrms
  • Supply voltage range
    19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
  • Conductor cross section flexible
    0.2 mm² ... 1.5 mm²
  • Ambient temperature (operation)
    -20 °C ... 60 °C (Any mounting position)
  • Degree of protection
    IP20 (not assessed by UL)
  • Underload/overload signal range
    0 mA ... 24 mA (Extended transmission range for diagnostics)
  • Signal output
    Signal conditioner operation
  • Load/output load current output
    < 450 Ω (20 mA)
  • Conductor cross section AWG
    24 ... 16
  • Width
    12.5 mm
  • Depth
    114.5 mm
  • Permissible humidity (operation)
    10 % ... 95 % (non-condensing)
  • Transmitter supply voltage
    > 16 V (20 mA)
  • Nominal supply voltage
    24 V DC
  • Power dissipation
    < 1.2 W (24 V DC / 20 mA)
  • Stripping length
    8 mm
  • Maximum transmission error
    < 0.1 % (of final value)
  • Step response (10-90%)
    1.3 ms (for jump 4 mA ... 20 mA, typical)
  • Voltage drop
    approx. 3.9 V (in input isolating amplifier operation)
  • Maximum altitude
    ≤ 2000 m
  • Current input signal
    0 A ... 20 mA
  • Current output signal
    0 mA ... 20 mA (active)
  • Max. current consumption
    < 46 mA (24 V DC / 20 mA)
  • Conductor cross section solid
    0.2 mm² ... 1.5 mm²
  • Utilization restriction
    EMC: class A product, see manufacturer's declaration in the download area
  • No. of channels
    1
  • Transmission error, typical
    < 0.05 % (of final value)
  • Housing material
    PA 6.6-FR
  • UNSPSC 18.0
    39121008
  • UNSPSC 21.0
    39121008
  • Maximum temperature coefficient
    < 0.01 %/K
  • ECLASS 5.0
    27210100
  • Group
    IIC
  • Test voltage
    1.5 kV AC (50 Hz, 1 min.)
  • Vibration
    A
  • HART function
    Yes
  • Max. output power Po
    587 mW
  • Safety-related maximum voltage Um
    253 V AC (125 V DC)
  • Input current Ii
    ≤ 150 mA
  • ATEX
     II (1) G [Ex ia Ga] IIC
  • DNV GL-Vibration
    A
  • Identification
    [Ex ia Ga] IIC
  • Electromagnetic compatibility
    Conformance with EMC directive
  • Interference emission
    EN 61000-6-4
  • Status display
    Green LED (PWR supply voltage)
  • Degree of pollution
    2
  • Electrical isolation
    375 V (Peak value in accordance with IEC/EN 60079-11)
  • Max. output current Io
    93 mA
  • Max. external inductivity Lo
    10 µH
  • Noise emission
    EN 61000-6-4
  • Max. internal capacitance Ci
    negligible
  • DNV GL-Humidity
    B
  • Nominal supply voltage range
    19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
  • Color
    gray
  • Designation
    INMETRO
  • Insulation
    Safe isolation in accordance with IEC/EN 61010-1
  • Operation
    Signal conditioner operation
  • Additional text
    and EN 61326
  • Max. internal inductance Li
    negligible
  • Conformance
    CE-compliant, additionally EN 61326
  • DNV GL-Temperature
    B
  • UL, USA/Canada
    Class I Div 2; IS for Class I, II, III Div 1
  • DNV GL-EMC
    A
  • Temperature
    B
  • Certificate
    DNV 18.0139 X
  • Enclosure
    Required protection according to the Rules shall be provided upon installation on board
  • ECLASS 4.1
    27210100
  • ECLASS 10.0.1
    27210120
  • ECLASS 11.0
    27210120
  • Max. output voltage Uo
    25.2 V
  • Standards/regulations
    GB 3626.20
  • ECLASS 4.0
    27210100
  • ETIM 4.0
    EC002653
  • ETIM 7.0
    EC002653
  • UNSPSC 19.0
    39121008
  • Input voltage Ui
    ≤ 30 V
  • Humidity
    B
  • EMC
    A
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 5.1
    27210100
  • ECLASS 7.0
    27210120
  • UNSPSC 11
    39121008
  • UNSPSC 12.01
    39121008
  • DNV GL-Enclosure
    Required protection according to the Rules shall be provided upon installation on board
  • ETIM 6.0
    EC002653
  • UNSPSC 13.2
    39121008
  • Overvoltage category
    II
  • Max. external capacitance Co
    1 µF
  • IECEx
    [Ex ia Ga] IIC
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 9.0
    27210120
  • UNSPSC 6.01
    30211506
  • UNSPSC 20.0
    39121008
  • ECLASS 6.0
    27210100
  • UNSPSC 7.0901
    39121008

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.


Manufacturer warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

Fast Shipping & Delivery


Secure Payment Processing


Warranty


Responsive Customer Support


Need more details?

Feel free to chat with us

What can I help you find today?