2908700 Phoenix Contact Electrical Safety Devices

2908700 on Power Resource International
Phoenix Contact

Part#:2908700

Manufacturer:Phoenix Contact

Category:Electrical Safety Devices

Product Lifecycle:Active

Get a quick Quote!

Hybrid motor starter as an alternative to a conventional protective circuit. Starts 3~ AC motors up to 3 A, provides motor protection and emergency stop up to SIL 3/PL e. Group shut-down, supply, and relay extension possible via DIN rail connector.

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Safety Devices that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2908700 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Width
    22.5 mm
  • Maximum altitude
    ≤ 2000 m
  • Type of protection
    Reverse polarity protection
  • Switching threshold
    9.6 V (“0” signal)
  • Depth
    114 mm
  • Rated control circuit supply voltage US
    24 V DC
  • Rated actuating voltage UC
    24 V DC
  • Operating voltage range
    42 V AC ... 550 V AC
  • Load current range
    180 mA ... 3 A
  • Leakage current
    0 mA
  • Mounting position
    vertical (horizontal DIN rail, motor output below)
  • Mounting type
    DIN rail mounting
  • Operating voltage display
    Green LED
  • Stripping length
    8 mm
  • Conductor cross section flexible
    0.2 mm² ... 2.5 mm²
  • Torque
    0.5 Nm ... 0.6 Nm
  • Designation
    Category (ISO 13849)
  • FLA
    3 A (480 V AC)
  • Horsepower ratings
    0.5 hp (208 V AC)
  • ECLASS 7.0
    27024002
  • Ambient temperature (operation)
    -25 °C ... 55 °C
  • Degree of protection
    IP20
  • Input name
    Control input and enable input
  • Rated actuating current IC
    7 mA
  • Rated operating voltage Ue
    500 V AC
  • Mains frequency
    50/60 Hz
  • Contact type
    1 changeover contact
  • Operate threshold
    > 33 A
  • Minimum power dissipation
    0.88 W
  • Indication
    Red LED
  • Connection method
    Screw connection
  • Conductor cross section AWG
    24 ... 14
  • Overvoltage category
    III
  • Certificate
    NLDX.E228652
  • Category code
    NLDX / NRNT
  • ECLASS 10.0.1
    27370905
  • ECLASS 5.0
    27024000
  • ETIM 6.0
    EC001037
  • UNSPSC 13.2
    25173902
  • UNSPSC 19.0
    25173902
  • UNSPSC 21.0
    25173902
  • Height
    107 mm
  • Rated control supply current IS
    60 mA
  • Triggering voltage range
    19.2 V DC ... 30 V DC
  • Switching level
    < 5 V DC (For EMERGENCY STOP)
  • Identification
    ≤ 3
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 4.0
    27021100
  • ECLASS 9.0
    27370905
  • ETIM 7.0
    EC001037
  • Ambient temperature (storage/transport)
    -40 °C ... 80 °C
  • Control supply voltage range
    19.2 V DC ... 30 V DC
  • Note
    Confirmation: floating change-over contact, signal contact
  • Typical turn-off time
    < 30 ms
  • Output name
    Acknowledge output
  • Rated operating current Ie
    3 A (AC-51)
  • Switching capacity according to IEC 60947-5-1
    2 A (24 V, DC13)
  • Switching frequency
    ≤ 2 Hz (Load-dependent)
  • Maximum power dissipation
    4.1 W
  • Connection name
    Load circuit
  • Screw thread
    M3
  • Rated insulation voltage
    550 V
  • Degree of pollution
    2
  • SCCR
    100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
  • Group installation
    20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and stranded)
  • ECLASS 4.1
    27021100
  • ECLASS 6.0
    27024000
  • ETIM 3.0
    EC001037
  • UNSPSC 20.0
    25173902
  • Trigger characteristic in acc. with IEC 60947-4-2
    Class 10
  • Cooling time
    20 min. (for auto reset)
  • Response time
    < 0.5 s
  • Assembly instructions
    alignable, for spacing see derating
  • Operating mode
    100% operating factor
  • Status display
    Yellow LED
  • Conductor cross section solid
    0.2 mm² ... 2.5 mm²
  • Rated surge voltage
    6 kV
  • Insulation
    Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
  • Standards/regulations
    EN 60947-1
  • Additional text
    Safe shutdown
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 11.0
    27370905
  • ECLASS 5.1
    27024000
  • ETIM 2.0
    EC001037
  • UNSPSC 18.0
    25173902
  • ETIM 4.0
    EC001037

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.


Manufacturer warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

Fast Shipping & Delivery


Secure Payment Processing


Warranty


Responsive Customer Support


Need more details?

Feel free to chat with us

What can I help you find today?