2908672 Phoenix Contact Data & Networking Devices

2908672 on Power Resource International
Phoenix Contact

Part#:2908672

Manufacturer:Phoenix Contact

Category:Data & Networking Devices

Product Lifecycle:Active

Get a quick Quote!

Networkable hybrid motor starter for starting 3~ AC motors up to 500 V AC and 9 A output current, with adjustable overload shutdown, emergency stop function up to SIL 3/PL e, and Push-in connection. Connection to IO-Link.

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Data & Networking Devices that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2908672 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • ECLASS 6.0
    27024000
  • ETIM 4.0
    EC001037
  • UNSPSC 7.0901
    39121514
  • Input name
    Enable input
  • Rated actuating current IC
    7 mA
  • Typical turn-off time
    < 30 ms
  • Motor starter type
    Direct starter
  • Operating mode
    100% operating factor
  • Designation
    Category (ISO 13849)
  • Category code
    NLDX / NRNT
  • ECLASS 11.0
    27370905
  • ECLASS 7.0
    27024002
  • ECLASS 9.0
    27370905
  • UNSPSC 18.0
    25173902
  • Rated actuating voltage UC
    24 V DC
  • Switching level
    < 5 V DC (For EMERGENCY STOP)
  • Mounting type
    DIN rail mounting
  • Operating voltage display
    Green LED
  • Indication
    Red LED
  • ECLASS 4.1
    27021100
  • ETIM 3.0
    EC001037
  • ETIM 7.0
    EC001037
  • ETIM 6.0
    EC001037
  • UNSPSC 19.0
    25173902
  • Triggering voltage range
    19.2 V DC ... 30 V DC
  • Rated operating voltage Ue
    500 V AC
  • Mains frequency
    50/60 Hz
  • Cooling time
    20 min. (for auto reset)
  • Assembly instructions
    alignable, for spacing see derating
  • Connection name
    Load circuit
  • ECLASS 10.0.1
    27370905
  • ECLASS 5.0
    27024000
  • ETIM 2.0
    EC001037
  • UNSPSC 11
    39121514
  • UNSPSC 21.0
    25173902
  • Depth
    114 mm
  • Output name
    AC output
  • Leakage current
    0 mA
  • Maximum power dissipation
    7 W
  • Connection method
    Push-in connection
  • Conductor cross section AWG
    24 ... 14
  • Additional text
    Safe shutdown
  • ECLASS 4.0
    27021100
  • ECLASS 5.1
    27024000
  • UNSPSC 6.01
    30211915
  • UNSPSC 12.01
    39121514
  • UNSPSC 20.0
    25173902
  • Switching threshold
    9.6 V (“0” signal)
  • Trigger characteristic in acc. with IEC 60947-4-2
    Class 10A
  • Mounting position
    vertical (horizontal DIN rail, motor output below)
  • Status display
    Yellow LED
  • Certificate
    NLDX.E228652
  • Width
    22.5 mm
  • Maximum altitude
    ≤ 2000 m
  • Rated control supply current IS
    65 mA
  • Rated operating current Ie
    9 A (AC-51)
  • Response time
    < 0.5 s
  • Stripping length
    10 mm
  • Note
    If this device is to be used in combination with the CrossPowerSystem power distribution board, the device mount for the 16 A fuse (order designation: EM-CPS-DA-22,5F/16A; order number: 1002668) is required in order to attach the hybrid motor starter to t
  • Ambient temperature (operation)
    -5 °C ... 55 °C (observe derating)
  • Degree of protection
    IP20
  • Operate threshold
    > 60 A
  • Minimum power dissipation
    0.88 W
  • Rated surge voltage
    6 kV
  • Type of note
    Notes on operation
  • Ambient temperature (storage/transport)
    -40 °C ... 80 °C
  • Operating voltage range
    42 V AC ... 550 V AC
  • Load current range
    1.5 A ... 9 A (see to derating)
  • Conductor cross section flexible
    0.2 mm² ... 2.5 mm²
  • Overvoltage category
    III
  • Height
    127 mm
  • Rated control circuit supply voltage US
    24 V DC
  • Control supply voltage range
    19.2 V DC ... 30 V DC
  • UNSPSC 13.2
    25173902
  • Degree of pollution
    2
  • Switching frequency
    ≤ 2 Hz (Load-dependent)
  • Conductor cross section solid
    0.2 mm² ... 2.5 mm²
  • Rated insulation voltage
    550 V
  • SCCR
    100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
  • Type of protection
    Surge protection
  • Insulation
    Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
  • Group installation
    20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and stranded)
  • Horsepower ratings
    2 hp (208 V AC)
  • Standards/regulations
    IEC 60947-1
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • Identification
    ≤ 3
  • REACh SVHC
    Lead 7439-92-1
  • FLA
    7.6 A (480 V AC)

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.


Manufacturer warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

Fast Shipping & Delivery


Secure Payment Processing


Warranty


Responsive Customer Support


Need more details?

Feel free to chat with us

What can I help you find today?