2908672 Phoenix Contact Data & Networking Devices
Part#:2908672
Manufacturer:Phoenix Contact
Category:Data & Networking Devices
Product Lifecycle:Active
Get a quick Quote!
Networkable hybrid motor starter for starting 3~ AC motors up to 500 V AC and 9 A output current, with adjustable overload shutdown, emergency stop function up to SIL 3/PL e, and Push-in connection. Connection to IO-Link.
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Data & Networking Devices that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2908672 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- ECLASS 6.0 27024000
- ETIM 4.0 EC001037
- UNSPSC 7.0901 39121514
- Input name Enable input
- Rated actuating current IC 7 mA
- Typical turn-off time < 30 ms
- Motor starter type Direct starter
- Operating mode 100% operating factor
- Designation Category (ISO 13849)
- Category code NLDX / NRNT
- ECLASS 11.0 27370905
- ECLASS 7.0 27024002
- ECLASS 9.0 27370905
- UNSPSC 18.0 25173902
- Rated actuating voltage UC 24 V DC
- Switching level < 5 V DC (For EMERGENCY STOP)
- Mounting type DIN rail mounting
- Operating voltage display Green LED
- Indication Red LED
- ECLASS 4.1 27021100
- ETIM 3.0 EC001037
- ETIM 7.0 EC001037
- ETIM 6.0 EC001037
- UNSPSC 19.0 25173902
- Triggering voltage range 19.2 V DC ... 30 V DC
- Rated operating voltage Ue 500 V AC
- Mains frequency 50/60 Hz
- Cooling time 20 min. (for auto reset)
- Assembly instructions alignable, for spacing see derating
- Connection name Load circuit
- ECLASS 10.0.1 27370905
- ECLASS 5.0 27024000
- ETIM 2.0 EC001037
- UNSPSC 11 39121514
- UNSPSC 21.0 25173902
- Depth 114 mm
- Output name AC output
- Leakage current 0 mA
- Maximum power dissipation 7 W
- Connection method Push-in connection
- Conductor cross section AWG 24 ... 14
- Additional text Safe shutdown
- ECLASS 4.0 27021100
- ECLASS 5.1 27024000
- UNSPSC 6.01 30211915
- UNSPSC 12.01 39121514
- UNSPSC 20.0 25173902
- Switching threshold 9.6 V (“0” signal)
- Trigger characteristic in acc. with IEC 60947-4-2 Class 10A
- Mounting position vertical (horizontal DIN rail, motor output below)
- Status display Yellow LED
- Certificate NLDX.E228652
- Width 22.5 mm
- Maximum altitude ≤ 2000 m
- Rated control supply current IS 65 mA
- Rated operating current Ie 9 A (AC-51)
- Response time < 0.5 s
- Stripping length 10 mm
- Note If this device is to be used in combination with the CrossPowerSystem power distribution board, the device mount for the 16 A fuse (order designation: EM-CPS-DA-22,5F/16A; order number: 1002668) is required in order to attach the hybrid motor starter to t
- Ambient temperature (operation) -5 °C ... 55 °C (observe derating)
- Degree of protection IP20
- Operate threshold > 60 A
- Minimum power dissipation 0.88 W
- Rated surge voltage 6 kV
- Type of note Notes on operation
- Ambient temperature (storage/transport) -40 °C ... 80 °C
- Operating voltage range 42 V AC ... 550 V AC
- Load current range 1.5 A ... 9 A (see to derating)
- Conductor cross section flexible 0.2 mm² ... 2.5 mm²
- Overvoltage category III
- Height 127 mm
- Rated control circuit supply voltage US 24 V DC
- Control supply voltage range 19.2 V DC ... 30 V DC
- UNSPSC 13.2 25173902
- Degree of pollution 2
- Switching frequency ≤ 2 Hz (Load-dependent)
- Conductor cross section solid 0.2 mm² ... 2.5 mm²
- Rated insulation voltage 550 V
- SCCR 100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
- Type of protection Surge protection
- Insulation Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
- Group installation 20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and stranded)
- Horsepower ratings 2 hp (208 V AC)
- Standards/regulations IEC 60947-1
- China RoHS Environmentally Friendly Use Period = 50 years
- Identification ≤ 3
- REACh SVHC Lead 7439-92-1
- FLA 7.6 A (480 V AC)
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Manufacturer warranty
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
Fast Shipping & Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Need more details?
Feel free to chat with us
What can I help you find today?