2907071 Phoenix Contact UPS (DC)
Part#:2907071
Manufacturer:Phoenix Contact
Category:UPS (DC)
Product Lifecycle:Active
Get a quick Quote!
QUINT UPS with IQ Technology, for DIN rail mounting, input: 24 V DC, output: 24 V DC / 20 A, charging current: 5 A
About the manufacturer: Phoenix Contact is one of the manufacturers that offers UPS (DC) that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2907071 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Weight 0.6 kg
- Height with alternative assembly 130 mm
- Installation distance right/left (active) 5 mm / 5 mm (POut ≥50% )
- Degree of protection IP20
- Ambient temperature (start-up type tested) -40 °C
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Internal input fuse no
- Short-circuit-proof yes
- Energy storage device connection in parallel Yes, 5 (observe line protection)
- Dynamic Boost (IDyn.Boost) 30 A (5 s)
- Nominal capacity (without additional charger) 3 Ah ... 135 Ah
- Buffer time 22 min. (12 Ah)
- Temperature sensor yes
- Single conductor/terminal point, stranded, with ferrule, min. 0.2 mm²
- Conductor cross section flexible max. 4 mm²
- Stripping length 8 mm
- EMC requirements for noise emission EN 61000-6-3
- Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
- Comments Criterion A
- Height 130 mm
- Depth with alternative assembly 42 mm
- Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
- Climatic class 3K3 (EN 60721)
- Electric strength, max. 35 V DC (Protected against polarity reversal)
- No-load proof yes
- UPS connection in series no
- Static Boost (IStat.Boost) 25 A
- End-of-charge voltage (temperature-compensated) 25 V DC ... 32 V DC
- Charge characteristic curve IU0U
- Single conductor/terminal point, stranded, with ferrule, max. 4 mm²
- Tightening torque, min 0.5 Nm
- Identification IEC 61010-1
- Electromagnetic HF field EN 61000-4-3
- Discharge in air 15 kV (Test Level 4)
- Output 1 kV (Test Level 3 - symmetrical)
- ECLASS 9.0 27040705
- Width with alternative assembly 123 mm
- Installation distance top/bottom (active, passive) 40 mm / 20 mm (POut ≤50 %)
- Installation distance top/bottom (active) 50 mm / 50 mm (POut ≥50% )
- Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
- Installation height ≤ 4000 m
- Switch-over time 0 ms
- Input voltage 24 V DC
- Reverse polarity protection yes
- Energy storage device connection in series no
- Output voltage range 19 V DC ... 28 V DC (UOUT = UBAT - 0.4 V DC)
- IQ-Technology yes
- Conductor cross section AWG max. 12
- Standards/regulations IEC 61010-1 (SELV)
- Electrostatic discharge EN 61000-4-2
- Conducted interference EN 61000-4-6
- Frequency 0 Hz
- REACh SVHC Lead 7439-92-1
- ECLASS 5.1 27242213
- UNSPSC 18.0 39121011
- Switch-on time max. 3 s
- Selective Fuse Breaking (ISFB) 120 A (15 ms)
- Charging time 165 min. (12 Ah)
- Life expectancy (electrolytic capacitors) 192072 h
- Conductor cross section solid max. 6 mm²
- Conductor cross section AWG min. 30
- EMC requirements for noise immunity EN 61000-6-1
- Standard designation Safety extra-low voltage
- Test field strength 300 A/m
- Input 1 kV (Test Level 3 - symmetrical)
- Voltage 10 V (Test Level 3)
- Additional text DC, 60 s
- ECLASS 11.0 27040705
- ETIM 7.0 EC000382
- Inrush current ≤ 8 A (≤ 4 ms)
- Max. capacity 135 Ah
- MTBF (IEC 61709, SN 29500) > 1940000 h (25 °C)
- Connection method Screw connection
- Designation CB scheme
- Contact discharge 8 kV (Test Level 4)
- Fast transients (burst) EN 61000-4-4
- Criterion A Normal operating behavior within the specified limits.
- Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
- ETIM 6.0 EC000382
- Width 40 mm
- Depth 125 mm
- Installation distance right/left (active, passive) 0 mm / 0 mm (POut ≤50 %)
- Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
- Degree of pollution 2
- Input voltage range 18 V DC ... 30 V DC
- Fixed backup threshold 22 V DC
- Efficiency typ. 98 %
- Temperature compensation (configurable) 42 mV/K
- Conductor cross section flexible min. 0.2 mm²
- Tightening torque max 0.6 Nm
- Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
- Frequency range 50 Hz ... 60 Hz
- I/O/S asymmetrical
- ECLASS 10.0.1 27040705
- UNSPSC 13.2 39121004
- UNSPSC 20.0 39121011
- Installation distance right/left (passive) 0 mm / 0 mm (POut ≥50% )
- Installation distance top/bottom (passive) 40 mm / 20 mm (POut ≥50% )
- Voltage drop, input/output 0.4 V DC
- UPS connection in parallel no
- Battery technology VRLA, VRLA-WTR, LI-ION
- Charging current (configurable) max. 5 A
- Environmental protection directive RoHS Directive 2011/65/EU
- Conductor cross section solid min. 0.2 mm²
- Signal 1 kV (Test Level 2 - asymmetrical)
- Surge voltage load (surge) EN 61000-4-5
- Power frequency magnetic field EN 61000-4-8
- UNSPSC 19.0 39121011
- UNSPSC 21.0 39121011
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.