2906991 Phoenix Contact UPS (DC)
Part#:2906991
Manufacturer:Phoenix Contact
Category:UPS (DC)
Product Lifecycle:Active
Get a quick Quote!
QUINT UPS with IQ Technology, USB communication interface (Modbus/RTU), for DIN rail mounting, input: 24 V DC, output: 24 V DC / 5 A, charging current: 1.5 A
About the manufacturer: Phoenix Contact is one of the manufacturers that offers UPS (DC) that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2906991 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Weight 0.5 kg
- Height 130 mm
- Height with alternative assembly 130 mm
- Ambient temperature (start-up type tested) -40 °C
- Climatic class 3K3 (EN 60721)
- Input voltage 24 V DC
- Reverse polarity protection yes
- No-load proof yes
- Dynamic Boost (IDyn.Boost) 10 A (5 s)
- Output voltage range 19 V DC ... 32 V DC (UOUT = UBAT - 0.3 V DC)
- Charging time 2.5 h (3.4 Ah)
- Temperature sensor yes
- Conductor cross section solid max. 2.5 mm²
- Depth with alternative assembly 37 mm
- Installation distance right/left (passive) 0 mm / 0 mm (POut ≥50% )
- Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Inrush current ≤ 7 A (≤ 4 ms)
- Internal input fuse no
- Switch-over time 0 ms
- Energy storage device connection in series no
- Static Boost (IStat.Boost) 6.25 A
- End-of-charge voltage 32 V DC
- Charging current (configurable) max. 1.5 A
- Temperature compensation (configurable) 42 mV/K
- Conductor cross section AWG min. 30
- EMC requirements for noise immunity EN 61000-6-1
- Designation CB scheme
- Electrostatic discharge EN 61000-4-2
- Frequency range 50 Hz ... 60 Hz
- Comments Criterion A
- Frequency 0 Hz
- ECLASS 10.0.1 27040705
- ECLASS 9.0 27040705
- UNSPSC 18.0 39121011
- Width with alternative assembly 123 mm
- Installation distance top/bottom (active, passive) 40 mm / 20 mm (POut ≤50 %)
- Installation distance top/bottom (active) 50 mm / 50 mm (POut ≥50% )
- Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
- Installation height ≤ 4000 m
- Voltage drop, input/output 0.3 V DC
- Switch-on time max. 3 s
- UPS connection in series no
- End-of-charge voltage (temperature-compensated) 25 V DC ... 32 V DC
- Max. capacity 40 Ah
- MTBF (IEC 61709, SN 29500) > 1430000 h (25 °C)
- IQ-Technology yes
- Connection method Screw connection
- Stripping length 6.5 mm
- Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
- Contact discharge 8 kV (Test Level 4)
- Fast transients (burst) EN 61000-4-4
- Conducted interference EN 61000-4-6
- Power frequency magnetic field EN 61000-4-8
- Criterion A Normal operating behavior within the specified limits.
- REACh SVHC Lead 7439-92-1
- ETIM 7.0 EC000382
- Installation distance right/left (active) 5 mm / 5 mm (POut ≥50% )
- Degree of protection IP20
- Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
- Input voltage range 18 V DC ... 30 V DC
- Short-circuit-proof yes
- Energy storage device connection in parallel Yes, 5 (observe line protection)
- Selective Fuse Breaking (ISFB) 30 A (15 ms)
- Nominal capacity (without additional charger) 0.8 Ah ... 30 Ah
- Charge characteristic curve IU0U
- Life expectancy (electrolytic capacitors) 224011 h
- Conductor cross section flexible min. 0.2 mm²
- Single conductor/terminal point, stranded, with ferrule, min. 0.2 mm²
- Tightening torque max 0.6 Nm
- Identification IEC 61010-1
- Electromagnetic HF field EN 61000-4-3
- Output 1 kV (Test Level 3 - symmetrical)
- Surge voltage load (surge) EN 61000-4-5
- Additional text DC, 60 s
- ETIM 6.0 EC000382
- UNSPSC 19.0 39121011
- Installation distance right/left (active, passive) 0 mm / 0 mm (POut ≤50 %)
- Installation distance top/bottom (passive) 40 mm / 20 mm (POut ≥50% )
- Degree of pollution 2
- Electric strength, max. 35 V DC (Protected against polarity reversal)
- Fixed backup threshold 22 V DC
- UPS connection in parallel no
- Efficiency typ. 98 %
- Battery technology VRLA, VRLA-WTR, LI-ION
- Buffer time 25 min. (3.4 Ah)
- Environmental protection directive RoHS Directive 2011/65/EU
- Conductor cross section solid min. 0.2 mm²
- Conductor cross section flexible max. 2.5 mm²
- Conductor cross section AWG max. 12
- EMC requirements for noise emission EN 61000-6-3
- Standard designation Safety extra-low voltage
- Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
- Input 1 kV (Test Level 3 - symmetrical)
- I/O/S asymmetrical
- ECLASS 11.0 27040705
- UNSPSC 13.2 39121004
- UNSPSC 21.0 39121011
- Single conductor/terminal point, stranded, with ferrule, max. 2.5 mm²
- Tightening torque, min 0.5 Nm
- Standards/regulations IEC 61010-1 (SELV)
- Discharge in air 15 kV (Test Level 4)
- Test field strength 300 A/m
- Signal 1 kV (Test Level 2 - asymmetrical)
- Voltage 10 V (Test Level 3)
- Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
- ECLASS 5.1 27242213
- UNSPSC 20.0 39121011
- Depth 125 mm
- Width 35 mm
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Manufacturer warranty
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
Fast Shipping & Delivery
Secure Payment Processing
Warranty
Responsive Customer Support