2906876 Phoenix Contact Electrical Measuring & Monitoring Instruments
Part#:2906876
Manufacturer:Phoenix Contact
Category:Electrical Measuring & Monitoring Instruments
Product Lifecycle:Active
Get a quick Quote!
Universally configurable temperature limit value switch with two transistor outputs for the connection of 2, 3, and 4-conductor resistance thermometers and thermocouples. Configurable via DIP switch or software, screw connection technology
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2906876 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Height 109.81 mm
- Maximum altitude ≤ 2000 m
- Linear resistance measuring range 0 Ω ... 4000 Ω
- Max. switching current 100 mA (30 V)
- Maximum switching voltage 30 V DC
- Screw thread M3
- Conductor cross section flexible 0.14 mm² ... 2.5 mm²
- No. of channels 1
- Test voltage, input/output/supply 3 kV (50 Hz, 1 min.)
- Assembly instructions The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
- UL, USA/Canada UL 508 Listed
- Certificate DNV GL TAA000021E
- Temperature B
- ECLASS 4.1 27210100
- ETIM 6.0 EC002654
- UNSPSC 7.0901 39121008
- UNSPSC 13.2 39121008
- Depth 119.2 mm
- Width 6.2 mm
- Number of inputs 1
- Sensor input current approx. 200 µA
- Linear mV signal range -500 mV ... 500 mV
- Output name Switching output
- Supply voltage range 9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
- Connection method Screw connection
- Torque 0.5 Nm ... 0.6 Nm
- Status display Yellow LED (switching output)
- Housing material PBT
- Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
- DNV GL-Temperature B
- Designation Shipbuilding approval
- Ambient temperature (operation) -40 °C ... 70 °C
- Permissible humidity (operation) 5 % ... 95 % (non-condensing)
- Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
- Connection technology 2-, 3-, 4-conductor
- Sensor types (RTD) that can be used Pt, Ni, Cu sensors
- Number of outputs 2
- Nominal supply voltage 24 V DC
- Switching point accuracy < 0.1 %
- Rated insulation voltage 300 V
- Noise emission EN 61000-6-4
- Mounting position any
- ATEX II 3 G Ex nA IIC T4 Gc X
- DNV GL-Vibration A
- Identification UL 508 Listed
- Vibration A
- China RoHS Environmentally Friendly Use Period = 50 years
- Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Available input sources Thermocouples
- Sensor types that can be used (TC) B, E, J, K, N, R, S, T, L, U, A-1, A-2, A-3, M, L
- Power consumption 350 mW
- Stripping length 10 mm
- Conductor cross section AWG 24 ... 12 (flexible)
- Overvoltage category II
- Degree of pollution 2
- Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
- Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
- DNV GL-Humidity B
- DNV GL-EMC A
- EMC A
- ECLASS 10.0.1 27210122
- ECLASS 7.0 27210122
- UNSPSC 6.01 30211506
- UNSPSC 18.0 39121008
- Degree of protection IP20 (not assessed by UL)
- Max. permissible overall conductor resistance ≤ 25 Ω (Per line, RTD in 3- or 4-conductor technology)
- Contact type 2 N/O contacts
- Typical current consumption 20 mA (12 V DC)
- Conductor cross section solid 0.2 mm² ... 1.5 mm² (with ferrule)
- Maximum temperature coefficient 0.01 %/K
- Electrical isolation Reinforced insulation in accordance with IEC 61010-1
- Electromagnetic compatibility Conformance with EMC directive
- Color gray
- Conformance CE-compliant
- DNV GL-Enclosure Required protection according to the Rules shall be provided upon installation on board
- Humidity B
- REACh SVHC Lead 7439-92-1
- ECLASS 4.0 27210100
- ETIM 4.0 EC002654
- ETIM 7.0 EC002654
- UNSPSC 21.0 39121008
- Enclosure Required protection according to the Rules shall be provided upon installation on board
- ECLASS 11.0 27210122
- ECLASS 5.0 27210100
- ECLASS 9.0 27210122
- UNSPSC 12.01 39121008
- UNSPSC 19.0 39121008
- ECLASS 5.1 27210100
- ECLASS 6.0 27210100
- UNSPSC 11 39121008
- UNSPSC 20.0 39121008
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Manufacturer warranty
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
Fast Shipping & Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Need more details?
Feel free to chat with us
What can I help you find today?