Hybrid motor starter for starting 3~ AC motors up to 550 V AC, with 24 V DC input, 9 A output current, emergency stop function, adjustable overload shutdown, higher transient voltage strength, and push-in connection.

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Safety Devices that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2906064 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Ambient temperature (storage/transport)
    -40 °C ... 80 °C
  • Type of protection
    Surge protection
  • Load current range
    1.5 A ... 9 A (see to derating)
  • Switching capacity according to IEC 60947-5-1
    3 A (230 V, AC15)
  • Switching frequency
    ≤ 2 Hz (Load-dependent)
  • Mounting position
    vertical (horizontal DIN rail, motor output below)
  • Status display
    Yellow LED
  • Height
    107.5 mm
  • Maximum altitude
    ≤ 2000 m
  • Input name
    Control input
  • Switching threshold
    9.6 V (“0” signal)
  • Operating voltage range
    42 V AC ... 550 V AC
  • Rated operating current Ie
    9 A (AC-51)
  • Cooling time
    20 min.
  • Response time
    2 s
  • Operating mode
    100% operating factor
  • Stripping length
    10 mm
  • Conductor cross section AWG
    24 ... 14
  • Certificate
    NLDX.E228652
  • Category code
    NLDX / NRNT
  • ECLASS 4.0
    27021100
  • ECLASS 5.0
    27024000
  • Width
    22.5 mm
  • Degree of protection
    IP20
  • Rated control supply current IS
    40 mA
  • Rated actuating voltage UC
    24 V DC
  • Switching level
    < 5 V DC (For EMERGENCY STOP)
  • Rated operating voltage Ue
    500 V AC
  • Leakage current
    0 mA
  • Contact type
    1 changeover contact
  • Motor starter type
    Direct starter
  • Maximum power dissipation
    14.6 W
  • Connection method
    Push-in connection
  • Connection name
    Load circuit
  • Degree of pollution
    2
  • Identification
    ≤ 3
  • ECLASS 10.0.1
    27370905
  • ECLASS 4.1
    27021100
  • ECLASS 5.1
    27024000
  • ECLASS 7.0
    27024002
  • ETIM 3.0
    EC001037
  • ETIM 7.0
    EC001037
  • UNSPSC 19.0
    25173902
  • UNSPSC 18.0
    25173902
  • UNSPSC 21.0
    25173902
  • Depth
    114 mm
  • Control supply voltage range
    19.2 V DC ... 30 V DC
  • Rated actuating current IC
    5 mA
  • Output name
    Acknowledge output
  • Trigger characteristic in acc. with IEC 60947-4-2
    Class 10A
  • Assembly instructions
    alignable, for spacing see derating
  • Operating voltage display
    Green LED
  • Indication
    Red LED
  • Overvoltage category
    III
  • Insulation
    Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
  • Additional text
    Safe shutdown
  • REACh SVHC
    Lead 7439-92-1
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 6.0
    27024000
  • ECLASS 9.0
    27370905
  • ETIM 2.0
    EC001037
  • ETIM 6.0
    EC001037
  • ETIM 4.0
    EC001037
  • UNSPSC 13.2
    25173902
  • UNSPSC 20.0
    25173902
  • Ambient temperature (operation)
    5 °C ... 70 °C (observe derating)
  • Rated control circuit supply voltage US
    24 V DC
  • Triggering voltage range
    19.2 V DC ... 30 V DC
  • Typical turn-off time
    < 30 ms
  • Mains frequency
    50/60 Hz
  • Note
    Confirmation: floating change-over contact, signal contact
  • Operate threshold
    > 45 A
  • Mounting type
    DIN rail mounting
  • Minimum power dissipation
    1.1 W
  • Conductor cross section solid
    0.2 mm² ... 2.5 mm²
  • Rated insulation voltage
    500 V
  • Designation
    Category (ISO 13849)
  • Group installation
    20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded)
  • ECLASS 11.0
    27370905
  • Conductor cross section flexible
    0.2 mm² ... 2.5 mm²
  • Rated surge voltage
    6 kV
  • Standards/regulations
    IEC 60947-1
  • SCCR
    100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
  • FLA
    6.5 A (480 V AC)

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.


Manufacturer warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

Fast Shipping & Delivery


Secure Payment Processing


Warranty


Responsive Customer Support


Need more details?

Feel free to chat with us

What can I help you find today?