2905909 Phoenix Contact UPS (DC)
Part#:2905909
Manufacturer:Phoenix Contact
Category:UPS (DC)
Product Lifecycle:Active
Get a quick Quote!
1AC/1AC/750 VA uninterruptible power supply with integrated energy storage, lead AGM, VRLA technology, 24 V DC, 3.4 Ah for 230 V AC applications.
About the manufacturer: Phoenix Contact is one of the manufacturers that offers UPS (DC) that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2905909 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Weight 5.7 kg
- Ambient temperature (operation) 0 °C ... 40 °C
- Degree of pollution 2
- Climatic class 3K3 (in acc. with EN 60721)
- Conductor cross section solid min. 0.2 mm²
- Conductor cross section AWG min. 24
- Power factor (cos phi) 0.8
- Switch-over time < 10 ms
- Nominal output current (IN) 3 A (750 VA)
- Frequency (after automatic detection in mains operation) 50 Hz
- Hood version PC + ABS
- Input fuse 10 A 400 V gRL
- Charging time 7 h
- Depth 136 mm
- Installation distance top/bottom 50 mm / 50 mm
- Maximum altitude ≤ 3000 m (> 2000 m, observe derating)
- Installation distance right/left 0 mm / 0 mm
- Vibration (operation) 5 Hz ... 100 Hz, 0.7g (EN 60068-2-6)
- Frequency range 0.15 MHz ... 80 MHz
- Permissible backup fuse B6 B10 B16
- Conductor cross section flexible max. 1.5 mm²
- Conductor cross section AWG max. 16
- Nominal output voltage (UN) 230 V AC
- MTBF (IEC 61709, SN 29500) > 206000 h (40 °C)
- Type of housing DX51D+AZ (steel sheet / Galvalume)
- Capacity 3.4 Ah
- Accumulator type 2x Panasonic UP-VW1220P1
- Latest startup 6 Months (0 °C ... 20 °C)
- Buffer period 20 min. (100 W)
- Switching output Transistor output, active
- High signal Open (> 200 kΩ between bat. start and SGnd)
- Interface MINI-USB type B
- Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
- Electrostatic discharge EN 61000-4-2
- Comments Criterion A
- Output 1 kV (Test Level 2 - symmetrical)
- Power frequency magnetic field EN 61000-4-8
- Voltage 10 V
- Frequency 50 Hz
- ECLASS 4.0 27040600
- ECLASS 5.0 27040600
- ECLASS 7.0 27040602
- ECLASS 6.0 27040600
- UNSPSC 20.0 39121011
- Height 170 mm
- Ambient temperature (storage/transport) -15 °C ... 40 °C (with charged energy storage device)
- Shock 20g in all directions (EN 60068-2-27)
- Input voltage range 184 V AC ... 264 V AC
- Connection method Push-in connection
- Conductor cross section flexible min. 0.2 mm²
- Apparent power 750 VA
- Rated Power (Real Power) 600 W
- Form of output voltage Pure sine
- Efficiency > 95 % (with charged energy storage device)
- Degree of protection IP20
- Protection class I
- Battery technology Lead rechargeable battery module
- Service life 6 Years ... 9 Years (20 °C)
- Can be extended with external battery 1x 24 V 3.4 Ah
- Continuous load current ≤ 20 mA
- Designation Remote
- UPS connection in series no
- UPS connection in parallel no
- Electromagnetic HF field EN 61000-4-3
- Discharge in air 8 kV (Test Level 3)
- Test field strength 100 A/m
- Surge voltage load (surge) EN 61000-4-5
- Criterion A Normal operating behavior within the specified limits.
- REACh SVHC Lead 7439-92-1
- China RoHS Environmentally Friendly Use Period = 3
- ECLASS 10.0.1 27040705
- ECLASS 5.1 27040600
- ETIM 7.0 EC000382
- UNSPSC 19.0 39121011
- UNSPSC 21.0 39121011
- Width 210 mm
- Max. permissible relative humidity (operation) ≤ 95 % (25 °C, non-condensing)
- Nominal input voltage 230 V AC
- Current consumption 3 A
- Conductor cross section solid max. 1.5 mm²
- Stripping length 8 mm
- Crest factor 2.8
- Classification according to IEC 62040-3 VFD-SS-311
- Battery fuse 40 A, 32 V
- Output voltage 24 V (SELV)
- Status display LED red
- Low signal Connection to SGnd with < 2.7 kΩ
- Standard uninterruptible power supply systems EN 62040-1
- Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
- Contact discharge 6 kV (Test Level 3)
- Input 1 kV (Test Level 2 - symmetrical)
- Fast transients (burst) EN 61000-4-4
- Conducted interference EN 61000-4-6
- Signal 1 kV (Test Level 2 - asymmetrical)
- Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
- ECLASS 11.0 27040705
- ECLASS 4.1 27040600
- ECLASS 9.0 27040705
- ETIM 6.0 EC000382
- UNSPSC 18.0 39121011
- UNSPSC 13.2 39121011
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Manufacturer warranty
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
Fast Shipping & Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Need more details?
Feel free to chat with us
What can I help you find today?