Safety relay for monitoring non-equivalent signal generators up to SILCL 3, Cat. 4, PL e, 2-channel, non-equivalent operation, manual, monitored start, 1 enabling current path, US = 24 V DC, fixed screw terminal block
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Safety Devices that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2904957 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Width 6.8 mm
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Rated control circuit supply voltage US 24 VÂ DC -15 % / +10 %
- Input voltage range "0" signal 0 VÂ DC ... 5 VÂ DC (for safe Off; at S12)
- Input voltage range "1" signal 20.4 VÂ DC ... 26.4 VÂ DC
- Limiting continuous current 6 A (observe derating)
- Switching frequency max. 0.5 Hz
- Current max. 100 mA
- Typical response time at US < 175 ms
- Recovery time < 500 ms
- Min. degree of protection of inst. location IP54
- Status display 2 x green LEDs
- Stripping length 12 mm
- Stop category 0
- Rated insulation voltage 250 VÂ AC
- ECLASS 10.0.1 27371819
- ECLASS 5.0 27371900
- ECLASS 7.0 27371819
- UNSPSC 20.0 39122205
- Depth 102.5 mm
- Maximum altitude ≤ 2000 m (Above sea level)
- Power consumption at US typ. 1 W
- Input name Start circuit
- Max. permissible overall conductor resistance 150 Ω
- Protective circuit/component Suppressor diode
- Contact type 1 enabling current path
- Switching capacity min. 60 mW
- Voltage 22 V DC (Us - 2 V)
- Maximum inrush current 500 mA (Δt = 1 ms at Us)
- Relay type Electromechanical relay with force-guided contacts in accordance with IEC/ENÂ 61810-3
- Typical release time at US < 20 ms (when controlled via A1 or S12 and S13.)
- Degree of protection IP20
- Operating voltage display 1 x green LED
- Conductor cross section solid 0.2 mm² ... 2.5 mm²
- Screw thread M3
- Safety Integrity Level Claim Limit (SIL CL) 3
- Degree of pollution 2
- Vibration (operation) 10 Hz ... 150 Hz, 2g
- ECLASS 4.0 40020600
- ETIM 6.0 EC001449
- ETIM 7.0 EC001449
- Height 93.1 mm
- Max. permissible humidity (storage/transport) 75 % (on average, 85% infrequently, non-condensing)
- Inrush current min. 3 mA
- Protective circuit Surge protection Suppressor diode
- Number of inputs 1
- Output description non-safety-related
- Contact material AgSnO2
- Output fuse 6 A gL/gG (N/O contact)
- Short-circuit protection no
- Mounting type DIN rail mounting
- pluggable no
- Conductor cross section flexible 0.2 mm² ... 2.5 mm²
- Standards/regulations DINÂ ENÂ 50178
- Rated surge voltage/insulation Safe isolation, reinforced insulation 6Â kV between input circuit and enabling current pathBasic insulation 4Â kV between all current paths and housing
- REACh SVHC Lead 7439-92-1
- ECLASS 4.1 40020600
- ECLASS 9.0 27371819
- UNSPSC 21.0 39122205
- Ambient temperature (operation) -40 °C ... 60 °C (observe derating)
- Rated control supply current IS typ. 42 mA
- Description of the input non-safety-related
- Input current range "0" signal 0 mA ... 2 mA (for safe Off; at S12)
- Number of outputs 1 (digital, PNP)
- Sq. Total current 36 A2 (observe derating)
- Typical pickup time at US < 250 ms (when controlled via A1)
- Net weight 69 g
- Housing material PBT
- Conductor cross-section AWG 24 ... 12
- Performance level (PL) e (4Â AÂ DC13; 5Â AÂ AC15; 8760Â switching cycles/year)
- Overvoltage category III
- Shock 15g
- China RoHS Environmentally Friendly Use Period = 50 years
- UNSPSC 13.2 39121501
- UNSPSC 19.0 39122205
- Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
- Max. permissible relative humidity (operation) 75 % (on average, 85% infrequently, non-condensing)
- Designation Air clearances and creepage distances between the power circuits
- Filter time max. 1.5 ms (at S12, S13; test pulse width)
- Current consumption < 10 mA
- Output name Enabling current path
- Switching voltage min. 12 V AC/DC
- Mechanical service life 10x 106 cycles
- Nominal operating mode 100% operating factor
- Mounting position vertical or horizontal
- Housing color yellow
- Connection method Screw connection
- Safety Integrity Level (SIL) 3
- Category 4
- Conformance CE-compliant
- ECLASS 11.0 27371819
- ECLASS 5.1 27371900
- ECLASS 6.0 27371800
- UNSPSC 18.0 39122205
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Manufacturer warranty
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
Fast Shipping & Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Need more details?
Feel free to chat with us
What can I help you find today?