2904375 Phoenix Contact AC/DC Power Supplies
Part#:2904375
Manufacturer:Phoenix Contact
Category:AC/DC Power Supplies
Product Lifecycle:Active
Get a quick Quote!
Primary-switched UNO POWER power supply for DIN rail mounting, input: 1-phase, output: 5 V DC/40 W
About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2904375 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Height 90 mm
- Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Input voltage range 85 V AC ... 264 V AC
- Width 35 mm
- Climatic class 3K3 (in acc. with EN 60721)
- Frequency range (fN) 50 Hz ... 60 Hz 10 %
- Mains buffering time > 30 ms (120 V AC)
- Power factor (cos phi) 0.49
- Nominal output voltage 5 V DC ±1 %
- Derating 55 °C ... 70 °C (2.5%/K)
- Connection in series yes
- Control deviation < 1 % (change in load, static 10 % ... 90 %)
- Maximum power dissipation in no-load condition < 0.3 W
- Degree of protection IP20
- Installation distance right/left 0 mm / 0 mm
- Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
- Inrush current < 30 A (typical)
- Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
- Protective circuit/component Varistor
- Connection in parallel Yes, for redundancy and increased capacity
- Feedback voltage resistance < 10 V DC
- Residual ripple < 100 mVPP (with nominal values)
- Output power 40 W
- Net weight 0.21 kg
- Insulation voltage input/output 4 kV AC (type test)
- Mounting position horizontal DIN rail NS 35, EN 60715
- Assembly instructions alignable: 0 mm horizontally, 30 mm vertically
- Conductor cross section flexible min. 0.2 mm²
- Stripping length 8 mm
- Screw thread M3
- Standard - Electrical safety IEC 62368-1/VDE 0805 (SELV)
- Standard – Limitation of mains harmonic currents EN 61000-3-2
- Mains variation/undervoltage EN 61000-4-11
- Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
- Discharge in air 8 kV (Test Level 3)
- Comments Criterion A
- Fast transients (burst) EN 61000-4-4
- Voltage dips EN 61000-4-11
- Depth 84 mm
- Installation distance top/bottom 30 mm / 30 mm
- Ambient temperature (operation) -25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K)
- Nominal input voltage range 100 V AC ... 240 V AC
- Current consumption 0.8 A (100 V AC)
- Input fuse 2 A (slow-blow, internal)
- Type of protection Transient surge protection
- Nominal output current (IN) 8 A (-25 °C ... 55 °C)
- Protection against overvoltage at the output (OVP) ≤ 10 V DC
- Typical response time < 1 s
- Efficiency typ. 84 % (120 V AC)
- MTBF (IEC 61709, SN 29500) > 1201000 h (40 °C)
- Foot latch material POM (Polyoxymethylen)
- Conductor cross section solid min. 0.2 mm²
- Conductor cross section solid max. 2.5 mm²
- Conductor cross section AWG max. 14
- EMC requirements for noise emission EN 61000-6-3
- Standard - Safety of transformers EN 61558-2-16
- Standard - Safe isolation DIN VDE 0100-410
- UL approvals UL/C-UL listed UL 508
- Electrostatic discharge EN 61000-4-2
- Contact discharge 6 kV (Test Level 3)
- Test field strength 10 V/m
- Input 2 kV (Test Level 3 - symmetrical)
- Voltage 10 V (Test Level 3)
- Conducted interference EN 61000-4-6
- ECLASS 11.0 27040701
- ECLASS 5.0 27049000
- ECLASS 5.1 27049000
- ECLASS 7.0 27049002
- UNSPSC 18.0 39121004
- UNSPSC 21.0 39121004
- Degree of pollution 2
- Nominal power consumption 97.1 VA
- Power loss nominal load max. < 7.5 W
- Protection class II (in closed control cabinet)
- Housing material Polycarbonate
- Connection method Screw connection
- Conductor cross section flexible max. 2.5 mm²
- Conductor cross section AWG min. 24
- EMC requirements for noise immunity EN 61000-6-1
- Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
- Standard – Safety extra-low voltage IEC 62368-1 (SELV) und EN 60204-1 (PELV)
- CSA CAN/CSA-C22.2 No. 60950-1-07
- Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
- Electromagnetic HF field EN 61000-4-3
- Frequency range 10 kHz ... 80 MHz
- Output 1 kV (Test Level 2 - symmetrical)
- Surge voltage load (surge) EN 61000-4-5
- Criterion A Normal operating behavior within the specified limits.
- ECLASS 10.0.1 27040701
- ECLASS 9.0 27040701
- ECLASS 6.0 27049000
- ETIM 7.0 EC002540
- UNSPSC 13.2 39121004
- UNSPSC 20.0 39121004
- Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
- China RoHS Environmentally Friendly Use Period = 25;
- ECLASS 4.0 27040700
- ECLASS 4.1 27040700
- ETIM 6.0 EC002540
- ETIM 4.0 EC000599
- UNSPSC 19.0 39121004
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Manufacturer warranty
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
Fast Shipping & Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Need more details?
Feel free to chat with us
What can I help you find today?