Primary-switched UNO POWER power supply for DIN rail mounting, input: 1-phase, output: 5 V DC/25 W
About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2904374 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Height 90 mm
- Degree of protection IP20
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Current consumption 0.53 A (100 V AC)
- Input fuse 2 A (slow-blow, internal)
- Protective circuit/component Varistor
- Feedback voltage resistance < 10 V DC
- Output power 25 W
- MTBF (IEC 61709, SN 29500) > 2174000 h (40 °C)
- Connection method Screw connection
- Conductor cross section solid min. 0.2 mm²
- Installation distance right/left 0 mm / 0 mm
- Ambient temperature (operation) -25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K)
- Nominal input voltage range 100 V AC ... 240 V AC
- Power factor (cos phi) 0.47
- Type of protection Transient surge protection
- Control deviation < 1 % (change in load, static 10 % ... 90 %)
- Power loss nominal load max. < 4.5 W
- Housing material Polycarbonate
- Assembly instructions alignable: 0 mm horizontally, 30 mm vertically
- Conductor cross section flexible max. 2.5 mm²
- Screw thread M3
- EMC requirements for noise emission EN 61000-6-3
- Standard - Electrical safety IEC 62368-1/VDE 0805 (SELV)
- Standard – Safety extra-low voltage IEC 62368-1 (SELV) und EN 60204-1 (PELV)
- CSA CAN/CSA-C22.2 No. 60950-1-07
- Contact discharge 6 kV (Test Level 3)
- Discharge in air 8 kV (Test Level 3)
- Test field strength 10 V/m
- Fast transients (burst) EN 61000-4-4
- Voltage 10 V (Test Level 3)
- China RoHS Environmentally Friendly Use Period = 25;
- ECLASS 11.0 27040701
- ECLASS 5.1 27049000
- ECLASS 7.0 27049002
- ECLASS 9.0 27040701
- UNSPSC 13.2 39121004
- UNSPSC 20.0 39121004
- Depth 84 mm
- Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
- Frequency range (fN) 50 Hz ... 60 Hz 10 %
- Mains buffering time > 35 ms (120 V AC)
- Nominal output current (IN) 5 A (-25 °C ... 55 °C)
- Residual ripple < 40 mVPP (with nominal values)
- Typical response time < 1 s
- Efficiency typ. 85 % (120 V AC)
- Insulation voltage input/output 4 kV AC (type test)
- Conductor cross section AWG min. 24
- Conductor cross section AWG max. 14
- Standard - Safety of transformers EN 61558-2-16
- Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
- Standard – Limitation of mains harmonic currents EN 61000-3-2
- Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
- Width 22.5 mm
- Installation distance top/bottom 30 mm / 30 mm
- Degree of pollution 2
- Input voltage range 85 V AC ... 264 V AC
- Inrush current < 30 A (typical)
- Nominal output voltage 5 V DC ±1 %
- Derating 55 °C ... 70 °C (2.5%/K)
- Maximum power dissipation in no-load condition < 0.3 W
- Protection class II (in closed control cabinet)
- Foot latch material POM (Polyoxymethylen)
- Conductor cross section solid max. 2.5 mm²
- Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
- Climatic class 3K3 (in acc. with EN 60721)
- Nominal power consumption 61.7 VA
- Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
- Connection in parallel Yes, for redundancy and increased capacity
- Connection in series yes
- Protection against overvoltage at the output (OVP) ≤ 10 V DC
- Net weight 0.15 kg
- Mounting position horizontal DIN rail NS 35, EN 60715
- Conductor cross section flexible min. 0.2 mm²
- Stripping length 8 mm
- EMC requirements for noise immunity EN 61000-6-1
- Mains variation/undervoltage EN 61000-4-11
- Standard - Safe isolation DIN VDE 0100-410
- UL approvals UL/C-UL listed UL 508
- Electrostatic discharge EN 61000-4-2
- Output 1 kV (Test Level 2 - symmetrical)
- Voltage dips EN 61000-4-11
- UNSPSC 18.0 39121004
- ETIM 4.0 EC000599
- UNSPSC 19.0 39121004
- Electromagnetic HF field EN 61000-4-3
- Comments Criterion A
- Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
- Criterion A Normal operating behavior within the specified limits.
- ECLASS 4.0 27040700
- ECLASS 5.0 27049000
- ETIM 7.0 EC002540
- UNSPSC 21.0 39121004
- Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
- Frequency range 10 kHz ... 80 MHz
- Input 2 kV (Test Level 3 - symmetrical)
- Surge voltage load (surge) EN 61000-4-5
- Conducted interference EN 61000-4-6
- ECLASS 10.0.1 27040701
- ECLASS 4.1 27040700
- ECLASS 6.0 27049000
- ETIM 6.0 EC002540
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Manufacturer warranty
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
Fast Shipping & Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Need more details?
Feel free to chat with us
What can I help you find today?