2902055 Phoenix Contact Electrical Measuring & Monitoring Instruments
Part#:2902055
Manufacturer:Phoenix Contact
Category:Electrical Measuring & Monitoring Instruments
Product Lifecycle:Active
Get a quick Quote!
Configurable temperature transducer with plug-in connection technology for connecting thermocouples. Configurable via DIP switch or software. Screw connection technology, standard configuration
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2902055 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Height 109.81 mm
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
- ECLASS 5.0 27200200
- ECLASS 5.1 27200200
- UNSPSC 12.01 39121008
- UNSPSC 20.0 41112105
- Ambient temperature (operation) -40 °C ... 70 °C
- Number of outputs 1
- Max. output voltage approx. 12.3 V
- Supply voltage range 9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
- Power consumption ≤ 850 mW (at IOUT = 20 mA, 9.6 V DC, 600 Ω load)
- Screw thread M3
- Overvoltage category II
- Electromagnetic compatibility Conformance with EMC directive
- Test voltage, input/output/supply 3 kV (50 Hz, 1 min.)
- ATEX II 3 G Ex nA IIC T4 Gc X
- Conformance CE-compliant
- Certificate DNV GL 14445-15HH
- ECLASS 7.0 27200206
- ECLASS 6.0 27200200
- UNSPSC 7.0901 39121008
- UNSPSC 6.01 30211506
- Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
- Configurable/programmable Yes
- Degree of protection IP20 (not assessed by UL)
- Voltage output signal 0 V ... 5 V (via DIP switch)
- Ripple < 10 mVrms
- Stripping length 10 mm
- Torque 0.5 Nm ... 0.6 Nm
- Protective circuit Transient protection
- Rated insulation voltage 300 V (effective)
- Housing material PBT
- Mounting position any
- UL, USA/Canada UL 508 Listed
- China RoHS Environmentally Friendly Use Period = 50 years
- ETIM 2.0 EC001446
- ETIM 6.0 EC002919
- UNSPSC 13.2 41112105
- Depth 119.2 mm
- Sensor types that can be used (TC) B, C, E, J, K, N, R, S, T, L, U, A-1, A-2, A-3, M, L
- Current output signal 0 mA ... 20 mA (via DIP switch)
- Short-circuit current < 31.5 mA
- Degree of pollution 2
- Noise emission EN 61000-6-4
- Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
- REACh SVHC Lead 7439-92-1
- ECLASS 4.0 27200200
- ECLASS 9.0 27210129
- ETIM 4.0 EC001446
- UNSPSC 11 39121008
- UNSPSC 18.0 41112105
- Temperature measuring range -250 °C ... 2500 °C (Range depends on sensor type, range can be set freely via software or in increments from -150°C to 1350°C via DIP switches)
- Load/output load voltage output ≥ 10 kΩ
- Load/output load current output ≤ 600 Ω (at 20 mA)
- Typical current consumption 32.7 mA (24 V DC)
- Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
- Typical deviation from the measuring range final value 0.05 %
- Conductor cross section AWG 24 ... 12 (flexible)
- Connection method Screw connection
- Conductor cross section flexible 0.14 mm² ... 2.5 mm²
- Max. output current 24.6 mA
- Electrical isolation Reinforced insulation in accordance with IEC 61010-1
- Assembly instructions The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
- ECLASS 11.0 27210129
- UNSPSC 21.0 41112105
- Width 6.2 mm
- Typical cold point errors 2 K (2 K + (0,2 K * ΔT))
- Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
- Standards/regulations EN 61000-4-6
- Conductor cross section solid 0.2 mm² ... 1.5 mm² (with ferrule)
- ETIM 7.0 EC002919
- Permissible humidity (operation) 5 % ... 95 % (non-condensing)
- Maximum temperature coefficient ≤ 0.01 %/K
- Designation Shipbuilding approval
- Identification C, EMC2
- ECLASS 4.1 27200200
- ETIM 3.0 EC001446
- UNSPSC 19.0 41112105
- Transmission error thermocouples 0.1% * 600 K / set measuring range; 0.1% > 600 K (C, E, J, K, N, T, L, U, M Gost, L Gost)
- ECLASS 10.0.1 27210129
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Manufacturer warranty
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
Fast Shipping & Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Need more details?
Feel free to chat with us
What can I help you find today?