2902039 Phoenix Contact Electrical Measuring & Monitoring Instruments

2902039 on Power Resource International
Phoenix Contact

Part#:2902039

Manufacturer:Phoenix Contact

Category:Electrical Measuring & Monitoring Instruments

Product Lifecycle:Active

Get a quick Quote!

3-way signal conditioner with plug-in connection technology and calibrated measuring range changeover for the electrical isolation of unipolar and bipolar analog signals. Input/output configurable via DIP switch. push-in connection technology, order confi

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2902039 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Height
    109.81 mm
  • Degree of protection
    IP20 (not assessed by UL)
  • Noise immunity
    EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
  • Current input signal
    0 mA ... 20 mA (via DIP switch)
  • Max. output current
    22 mA
  • Load/output load voltage output
    ≥ 10 kΩ
  • Designation
    Shipbuilding approval
  • EMC
    A
  • ECLASS 11.0
    27210120
  • ECLASS 7.0
    27210120
  • UNSPSC 19.0
    39121008
  • Enclosure
    Required protection according to the Rules shall be provided upon installation on board
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Configurable/programmable
    Yes
  • Input resistance of voltage input
    > 1000 kΩ
  • Number of outputs
    1
  • Conductor cross section flexible
    0.14 mm² ... 2.5 mm²
  • Mounting position
    any
  • Identification
    UL 508 Listed
  • ECLASS 4.1
    27210100
  • ETIM 6.0
    EC002653
  • Depth
    119.2 mm
  • Number of inputs
    1
  • Voltage output signal
    0 V ... 5 V (via DIP switch)
  • Ripple
    < 20 mVPP (at 600 Ω)
  • Typical current consumption
    25 mA (Current output, at 24 V DC incl. load)
  • Stripping length
    10 mm
  • Temperature
    B
  • Humidity
    B
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 5.1
    27210100
  • ECLASS 9.0
    27210120
  • UNSPSC 13.2
    39121008
  • UNSPSC 21.0
    39121008
  • Utilization restriction
    EMC: class A product, see manufacturer's declaration in the download area
  • Permissible humidity (operation)
    5 % ... 95 % (non-condensing)
  • max. input voltage
    33 V
  • Input resistance current input
    approx. 63 Ω (+0.7 V for test diode)
  • Load/output load current output
    ≤ 600 Ω (at 20 mA)
  • Standards/regulations
    EN 61000-4-6
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 4.0
    27210100
  • ECLASS 6.0
    27210100
  • ETIM 7.0
    EC002653
  • UNSPSC 20.0
    39121008
  • Voltage input signal
    0 V ... 5 V (via DIP switch)
  • Max. input current
    24 mA
  • Current output signal
    0 mA ... 20 mA (via DIP switch)
  • Nominal supply voltage
    24 V DC
  • Maximum temperature coefficient
    0.01 %/K
  • Vibration
    A
  • UNSPSC 18.0
    39121008
  • ECLASS 5.0
    27210100
  • ETIM 4.0
    EC002653
  • ECLASS 10.0.1
    27210120
  • Ambient temperature (operation)
    -40 °C ... 70 °C
  • Temperature coefficient, typical
    0.01 %/K
  • Certificate
    DNV GL TAA00002UA
  • Connection method
    Push-in connection
  • Conductor cross section solid
    0.2 mm² ... 2.5 mm² (with ferrule)
  • No. of channels
    1
  • Step response (10-90%)
    < 8.5 ms (with 30 Hz filter)
  • Supply voltage range
    9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
  • Limit frequency (3 dB)
    30 Hz (via DIP switch)
  • Protective circuit
    Transient protection
  • Maximum transmission error
    ≤ 0.1 % (of final value)
  • Width
    6.2 mm
  • Short-circuit current
    < 32 mA
  • Electrical isolation
    Reinforced insulation in accordance with IEC 61010-1
  • Power consumption
    ≤ 800 mW (at IOUT = 20 mA, 9.6 V DC, 600 Ω load)
  • Conductor cross section AWG
    24 ... 12 (flexible)
  • Test voltage, input/output/supply
    3 kV (50 Hz, 1 min.)
  • Noise emission
    EN 61000-6-4
  • Rated insulation voltage
    300 V (effective)
  • Housing material
    PBT
  • Electromagnetic compatibility
    Conformance with EMC directive
  • Color
    gray
  • Degree of pollution
    2
  • Fire protection for rail vehicles (DIN EN 45545-2) R23
    HL 1 - HL 2
  • Fire protection for rail vehicles (DIN EN 45545-2) R22
    HL 1 - HL 2
  • Assembly instructions
    The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
  • Fire protection for rail vehicles (DIN EN 45545-2) R24
    HL 1 - HL 2
  • Overvoltage category
    II

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.


Manufacturer warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

Fast Shipping & Delivery


Secure Payment Processing


Warranty


Responsive Customer Support


Need more details?

Feel free to chat with us

What can I help you find today?