2865010 Phoenix Contact Electrical Measuring & Monitoring Instruments
Part#:2865010
Manufacturer:Phoenix Contact
Category:Electrical Measuring & Monitoring Instruments
Product Lifecycle:Active
Get a quick Quote!
NAMUR signal conditioner for operating proximity sensors and switches. The signals are transferred to the control level using 2 isolated relay outputs (N/O contact). Line fault detection (LFD), 3-way electrical isolation, SIL 2, screw connection.
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2865010 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
- Ambient temperature (operation) -20 °C ... 60 °C (Any mounting position)
- Noise immunity EN 61000-6-2 EN 61326
- Switching output Relay output
- Height 112.5 mm
- Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
- Short-circuit current ~ 8 mA
- Contact material AgSnO2, hard gold-plated
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Non-load voltage ~ 8 V DC
- Switching points (unattenuated) > 2.1 mA (conductive)
- Nominal supply voltage 24 V DC
- Power consumption < 950 mW
- Permissible humidity (operation) 10 % ... 95 % (non-condensing)
- Available input sources NAMUR proximity sensors (EN 60947-5-6)
- Contact type 2 N/O contacts
- Maximum switching voltage 250 V AC (2 A)
- Supply voltage range 19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
- Stripping length 7 mm
- No. of channels 1
- Color gray
- Rated insulation voltage 300 Vrms
- Integrity requirement IEC 61508 - Low demand
- λSD 1 x 10-9 (1 FIT)
- λSU 2.48 x 10-7 (248 FIT)
- Noise emission EN 61000-6-4
- DNV GL-Temperature B
- Additional text and EN 61326-1
- Humidity B
- EMC B
- ECLASS 11.0 27210121
- ECLASS 7.0 27210121
- ETIM 6.0 EC001485
- UNSPSC 6.01 30211506
- UNSPSC 20.0 39121008
- Depth 114.5 mm
- Degree of protection IP20 (not assessed by UL)
- Line fault detection Break 0.05 mA < IIN < 0.35 mA
- Mechanical service life 107 cycles
- Maximum switching capacity 500 VA
- Connection method Screw connection
- Maximum altitude ≤ 2000 m
- Switching points (attenuated) < 1.2 mA (blocking)
- Switching hysteresis < 0.2 mA
- Switching frequency ≤ 20 Hz (without load)
- Max. current consumption 30 mA (24 V DC)
- Torque 0.5 Nm ... 0.6 Nm
- Housing material PA 6.6-FR
- Insulation Safe isolation in accordance with IEC/EN 61010-1
- Degree of pollution 2
- Safe Failure Fraction (SFF) 78 %
- UL, USA/Canada UL 508 Listed
- DNV GL-Humidity B
- DNV GL-EMC B
- China RoHS Environmentally Friendly Use Period = 50 years
- REACh SVHC Lead 7439-92-1
- ECLASS 4.1 27210100
- ECLASS 9.0 27210121
- ETIM 3.0 EC001485
- UNSPSC 12.01 39121008
- UNSPSC 18.0 39121008
- Width 12.5 mm
- Power dissipation < 950 mW
- Screw thread M3
- Conductor cross section AWG 24 ... 14
- Interference emission EN 61000-6-4
- Conductor cross section flexible 0.2 mm² ... 2.5 mm²
- Status display Green LED (supply voltage)
- Electromagnetic compatibility Conformance with EMC directive
- Test voltage 2.5 kV AC (50 Hz, 1 min.)
- Safety Integrity Level (SIL) 2
- Probability of a hazardous failure on demand (PFDAVG) 3.01 x 10-4 (1 year)
- Diagnostic coverage (DC) DCS = 0.4 %, DCD = 8 %
- DNV GL-Vibration A
- Identification 2
- Certificate DNV GL TAA00000AG
- Enclosure Required protection according to the Rules shall be provided upon installation on board
- ECLASS 4.0 27210100
- ECLASS 6.0 27210100
- ETIM 7.0 EC001485
- UNSPSC 11 39121008
- UNSPSC 19.0 39121008
- Conductor cross section solid 0.2 mm² ... 2.5 mm²
- Designation Safety Integrity Level (SIL, IEC 61508)
- Overvoltage category III
- Equipment type Type A
- λDD 6 x 10-9 (6 FIT)
- λDU 6.2 x 10-8 (62 FIT)
- Conformance CE-compliant, additionally EN 61326-1
- ATEX II 3 G Ex nA nC IIC T4 Gc X
- DNV GL-Enclosure Required protection according to the Rules shall be provided upon installation on board
- Temperature B
- Vibration A
- ECLASS 10.0.1 27210121
- ECLASS 5.0 27210100
- ECLASS 5.1 27210100
- ETIM 2.0 EC001485
- ETIM 4.0 EC001485
- UNSPSC 7.0901 39121008
- UNSPSC 13.2 39121008
- UNSPSC 21.0 39121008
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Manufacturer warranty
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
Fast Shipping & Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Need more details?
Feel free to chat with us
What can I help you find today?