2864406 Phoenix Contact Electrical Measuring & Monitoring Instruments

2864406 on Power Resource International
Phoenix Contact

Part#:2864406

Manufacturer:Phoenix Contact

Category:Electrical Measuring & Monitoring Instruments

Product Lifecycle:Active

Get a quick Quote!

MCR 3-way isolating amplifier, for electrical isolation of analog signals, with screw connection, input signal: 0(4) mA ... 20 mA, output signal: 0(4) mA ... 20 mA

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2864406 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Ambient temperature (operation)
    -20 °C ... 65 °C
  • Utilization restriction
    EMC: class A product, see manufacturer's declaration in the download area
  • Depth
    101.2 mm
  • Number of inputs
    1
  • Input resistance current input
    approx. 50 Ω
  • Ripple
    < 20 mVPP (at 500 Ω)
  • Stripping length
    12 mm
  • Conductor cross section solid
    0.2 mm² ... 2.5 mm²
  • No. of channels
    1
  • Limit frequency (3 dB)
    approx. 100 Hz
  • Protective circuit
    Transient protection
  • Noise emission
    EN 61000-6-4
  • Fire protection for rail vehicles (DIN EN 45545-2) R23
    HL 1 - HL 2
  • Designation
    Shipbuilding approval
  • Typical deviation from the measuring range final value
    10 %
  • Vibration
    B
  • EMC
    A
  • ECLASS 10.0.1
    27210120
  • ECLASS 4.0
    27210100
  • ECLASS 9.0
    27210120
  • UNSPSC 6.01
    30211506
  • UNSPSC 13.2
    39121008
  • UNSPSC 21.0
    39121008
  • Width
    6.2 mm
  • Maximum altitude
    ≤ 2000 m
  • Configurable/programmable
    no
  • Max. input current
    50 mA
  • Current output signal
    0 mA ... 20 mA
  • Max. current consumption
    < 20 mA
  • Screw thread
    M3
  • Temperature coefficient, typical
    < 0.002 %/K
  • Degree of pollution
    2
  • Test voltage, input/output/supply
    1.5 kV (50 Hz, 1 min.)
  • Housing material
    PBT
  • Assembly instructions
    The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
  • Identification
    UL 508 Recognized
  • Temperature
    B
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 5.1
    27210100
  • ECLASS 7.0
    27210120
  • ETIM 7.0
    EC002653
  • UNSPSC 12.01
    39121008
  • UNSPSC 19.0
    39121008
  • Height
    93.1 mm
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Degree of protection
    IP20
  • Current input signal
    0 mA ... 20 mA
  • Number of outputs
    1
  • Nominal supply voltage
    24 V DC
  • Power consumption
    < 450 mW
  • Connection method
    Screw connection
  • Conductor cross section AWG
    26 ... 12
  • Maximum temperature coefficient
    < 0.01 %/K
  • Electrical isolation
    Basic insulation according to EN 61010
  • Electromagnetic compatibility
    Conformance with EMC directive
  • Mounting position
    any
  • Standards/regulations
    EN 61000-4-6
  • Humidity
    B
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 11.0
    27210120
  • ECLASS 4.1
    27210100
  • ECLASS 5.0
    27210100
  • ETIM 4.0
    EC002653
  • UNSPSC 7.0901
    39121008
  • UNSPSC 18.0
    39121008
  • Permissible humidity (operation)
    5 % ... 95 % (non-condensing)
  • Noise immunity
    EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
  • Max. output current
    28 mA
  • Load/output load current output
    < 500 Ω (at 20 mA)
  • Supply voltage range
    19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
  • Conductor cross section flexible
    0.2 mm² ... 2.5 mm²
  • Maximum transmission error
    ≤ 0.1 % (of final value)
  • Step response (10-90%)
    approx. 3.2 ms
  • Overvoltage category
    II
  • Rated insulation voltage
    50 V AC/DC
  • Color
    green
  • Fire protection for rail vehicles (DIN EN 45545-2) R22
    HL 1 - HL 2
  • Fire protection for rail vehicles (DIN EN 45545-2) R24
    HL 1 - HL 2
  • Connection in acc. with standard
    CUL
  • Certificate
    DNV GL TAA000020N
  • Enclosure
    Required protection according to the Rules shall be provided upon installation on board
  • ECLASS 6.0
    27210100
  • ETIM 6.0
    EC002653
  • UNSPSC 11
    39121008
  • UNSPSC 20.0
    39121008

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.


Manufacturer warranty