2804856 Phoenix Contact Electrical Measuring & Monitoring Instruments

2804856 on Power Resource International
Phoenix Contact

Part#:2804856

Manufacturer:Phoenix Contact

Category:Electrical Measuring & Monitoring Instruments

Product Lifecycle:Active

Get a quick Quote!

Protective plug PT with protective circuit for 4 conductors of signal circuits grounded on one side. Nominal voltage: 48 V AC

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2804856 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Complete module height
    90 mm
  • Degree of protection
    IP20
  • Color
    jet black RAL 9005
  • Rated current
    300 mA (45 °C)
  • Operating effective current IC at UC
    ≤ 5 µA
  • Nominal pulse current Ian (10/1000) µs (line-earth)
    12 A
  • Residual voltage with Ian (10/1000) µs (line-signalground)
    ≤ 125 V
  • Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω system
    typ. 3.5 MHz
  • Max. required back-up fuse
    315 mA (T)
  • Tightening torque
    0.5 Nm
  • Standards/specifications
    IEC 61643-21 2000
  • ECLASS 4.0
    27130800
  • ETIM 3.0
    EC000943
  • UNSPSC 6.01
    30212010
  • UNSPSC 12.01
    39121610
  • UNSPSC 19.0
    39121620
  • Depth
    52 mm
  • Complete module width
    17.7 mm
  • Mounting type
    on base element
  • IEC test classification
    C1
  • Nominal discharge current In (8/20) µs (line-earth)
    10 kA
  • Max. discharge current Imax (8/20) µs maximum (line-earth)
    10 kA (per path)
  • Voltage protection level Up static (line-earth)
    ≤ 40 V (C2 - 10 kV / 5 kA with PT 4X1-BE)
  • Input attenuation aE, asym.
    0.5 dB (≤ 2.5 MHz / 50 Ω)
  • Cut-off frequency fg (3 dB), asym. (PE) in 600 Ω system
    typ. 900 kHz
  • Screw thread
    M3
  • Stripping length
    8 mm
  • ECLASS 10.0.1
    27130807
  • ECLASS 5.1
    27130800
  • ETIM 4.0
    EC000943
  • UNSPSC 18.0
    39121620
  • Height
    45 mm
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Flammability rating according to UL 94
    V-0
  • Direction of action
    Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
  • Total discharge current Itotal (8/20) µs
    20 kA
  • Output voltage limitation at 1 kV/µs (line-earth) spike
    ≤ 110 V (with PT 4X1-BE)
  • Cut-off frequency fg (3 dB), asym. (PE) in 50 Ω system
    typ. 10 MHz
  • Resistance per path
    4.7 Ω ±10 %
  • Connection method
    Screw connection (in connection with the base element)
  • Conductor cross section solid
    0.2 mm² ... 4 mm²
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 5.0
    27130800
  • ECLASS 7.0
    27130807
  • ETIM 2.0
    EC000943
  • ETIM 7.0
    EC000943
  • UNSPSC 13.2
    39121620
  • Width
    17.7 mm
  • Ambient temperature (operation)
    -40 °C ... 85 °C
  • Altitude
    ≤ 2000 m (amsl (above mean sea level))
  • Arrester can be tested with CHECKMASTER from software version:
    From SW rev. 3.17
  • Residual current IPE
    ≤ 1 µA (with PT 4X1+F-BE)
  • Maximum continuous voltage UC
    77 V DC
  • Residual voltage at In (line-earth)
    ≤ 160 V (spike)
  • Voltage protection level Up (line-earth)
    ≤ 150 V (C2 - 10 kV / 5 kA with PT 4X1-BE)
  • Capacity (line-earth)
    typ. 400 pF (with PT 4X1-BE)
  • Impulse durability (line-earth)
    C2 - 10 kV / 5 kA
  • Conductor cross section flexible
    0.2 mm² ... 2.5 mm²
  • ECLASS 11.0
    27130807
  • ECLASS 4.1
    27130800
  • ECLASS 9.0
    27130807
  • UNSPSC 7.0901
    39121610
  • UNSPSC 20.0
    39121620
  • Horizontal pitch
    1 Div.
  • Complete module depth
    65.5 mm
  • Housing material
    PA 6.6
  • Type
    Male
  • Nominal voltage UN
    48 V AC
  • Pulse discharge current Iimp (10/350) µs
    2.5 kA (per path)
  • Output voltage limitation at 1 kV/µs (line-earth) static
    ≤ 50 V (with PT 4X1+F-BE)
  • Response time tA (line-signalground)
    ≤ 1 ns (with PT 4X1+F-BE)
  • Response time tA (line-earth)
    ≤ 1 ns (with PT 4X1-BE)
  • Surge protection fault message
    none
  • Conductor cross section AWG
    24 ... 12
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 6.0
    27130800
  • ETIM 6.0
    EC000943
  • UNSPSC 11
    39121610
  • UNSPSC 21.0
    39121620

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.


Manufacturer warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

Fast Shipping & Delivery


Secure Payment Processing


Warranty


Responsive Customer Support


Need more details?

Feel free to chat with us

What can I help you find today?