Surge protection, consisting of protective plug and base element, with integrated multi-stage status indicator on the module for one 2-wire floating signal circuit. Indirect grounding via gas-filled surge arrester.

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2801256 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Ambient temperature (operation)
    -40 °C ... 70 °C
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Housing material
    PA 6.6
  • Mounting type
    DIN rail: 35 mm
  • Rated current
    1000 mA (40 °C)
  • Residual current IPE
    ≤ 1 µA
  • Pulse discharge current Iimp (10/350) µs (line-earth)
    2.5 kA
  • Voltage protection level Up static (line-signalground)
    ≤ 60 V (C2 - 10 kV / 5 kA)
  • Cut-off frequency fg (3 dB), sym. in 150 Ω system
    typ. 1.1 MHz
  • Max. required back-up fuse
    1 A (FF)
  • Pulse reset time (line-line)
    ≤ 4000 ms
  • Conductor cross section solid
    0.2 mm² ... 4 mm²
  • REACh SVHC
    Lead 7439-92-1
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 7.0
    27130807
  • ETIM 4.0
    EC000943
  • ETIM 7.0
    EC000943
  • UNSPSC 13.2
    39121620
  • UNSPSC 21.0
    39121620
  • Width
    17.7 mm
  • Degree of protection
    IP20
  • Type
    DIN rail module, two-section, divisible
  • Maximum continuous voltage UC
    30 V DC
  • Nominal discharge current In (8/20) µs (line-line)
    10 kA
  • Nominal discharge current In (8/20) µs (line-earth)
    10 kA
  • Response time tA (line-line)
    ≤ 1 ns
  • Response time tA (line-earth)
    ≤ 100 ns
  • Capacity (line-line)
    typ. 2 nF
  • Resistance per path
    1.2 Ω ±5 %
  • Impulse durability (line-earth)
    C1 - 1 kV / 500 A
  • Stripping length
    10 mm
  • Standards/specifications
    IEC 61643-21 2000 + A1:2008 + A2:2012
  • ECLASS 10.0.1
    27130807
  • ECLASS 6.0
    27130800
  • ECLASS 5.1
    27130800
  • UNSPSC 12.01
    39121610
  • UNSPSC 11
    39121610
  • Depth
    77.5 mm (incl. DIN rail 7.5 mm)
  • Flammability rating according to UL 94
    V-0
  • Direction of action
    Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
  • Nominal voltage UN
    24 V DC
  • Operating effective current IC at UC
    ≤ 1 mA (in the signal circuit)
  • Nominal discharge current In (8/20) µs (line-signal ground)
    10 kA
  • Voltage protection level Up (line-line)
    ≤ 80 V (C1 - 1 kV/500 A)
  • Voltage protection level Up (line-earth)
    ≤ 900 V (C1 - 1 kV/500 A)
  • Voltage protection level Up static (line-earth)
    ≤ 130 V (C2 - 10 kV / 5 kA)
  • Input attenuation aE, sym.
    typ. 0.3 dB (≤ 270 kHz/150 Ω)
  • Surge protection fault message
    Optical, multi-stage
  • Impulse durability (line-signalground)
    C1 - 1 kV / 500 A
  • Pulse reset time (line-earth)
    ≤ 30 ms
  • Pulse reset time (line-signalground)
    ≤ 2600 ms
  • ECLASS 11.0
    27130807
  • ECLASS 4.1
    27130800
  • ECLASS 5.0
    27130800
  • ETIM 6.0
    EC000943
  • UNSPSC 7.0901
    39121610
  • UNSPSC 18.0
    39121620
  • UNSPSC 20.0
    39121620
  • Height
    109.3 mm
  • Altitude
    ≤ 4000 m (amsl (above mean sea level))
  • Horizontal pitch
    1 Div.
  • Color
    jet black RAL 9005
  • Note
    Remote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector.
  • IEC test classification
    C1
  • Total discharge current Itotal (8/20) µs
    20 kA
  • Voltage protection level Up (line-signalground)
    ≤ 600 V (C1 - 1 kV/500 A)
  • Voltage protection level Up static (line-line)
    ≤ 65 V (C1 - 1 kV/500 A)
  • Response time tA (line-signalground)
    ≤ 100 ns
  • Impulse durability (line-line)
    C1 - 1 kV / 500 A
  • Connection method
    DIN rail NS35
  • Conductor cross section flexible
    0.2 mm² ... 2.5 mm²
  • Conductor cross section AWG
    24 ... 12
  • ECLASS 4.0
    27130800
  • ETIM 3.0
    EC000943
  • ECLASS 9.0
    27130807
  • UNSPSC 6.01
    30212010
  • UNSPSC 19.0
    39121620

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.


Manufacturer warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

Fast Shipping & Delivery


Secure Payment Processing


Warranty


Responsive Customer Support


Need more details?

Feel free to chat with us

What can I help you find today?