2702097 Phoenix Contact Electrical Safety Devices
Part#:2702097
Manufacturer:Phoenix Contact
Category:Electrical Safety Devices
Product Lifecycle:Active
Get a quick Quote!
Safety relay for emergency stop, safety doors, light grid up to SILCL 3, Cat. 4, PL e, 1- or 2-channel operation, cross-circuit detection, can be retriggered, fall back/on delay 0.2 s to 60 s, 2 enabling current paths, US = 24 V DC, pluggable Push-in term
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Safety Devices that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2702097 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
- Max. permissible humidity (storage/transport) 75 % (on average, 85% infrequently, non-condensing)
- Designation Air clearances and creepage distances between the power circuits
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Power consumption at US typ. 1.44 W
- Number of inputs 1
- Width 12.5 mm
- Rated control circuit supply voltage US 24 V DC -20 % / +25 %
- Inrush current min. 3 mA
- Description of the input non-safety-related
- Concurrence ∞
- Contact material AgSnO2
- Switching capacity min. 60 mW
- Short-circuit protection Yes
- Nominal operating mode 100% operating factor
- Relay type Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
- Housing color yellow
- pluggable Yes
- Stripping length 8 mm
- Performance level (PL) e
- Safety Integrity Level Claim Limit (SIL CL) 3
- Conformance CE-compliant
- ECLASS 4.1 40020600
- ECLASS 4.0 40020600
- ECLASS 5.1 27371900
- UNSPSC 20.0 39122205
- Depth 114.5 mm
- Height 116.6 mm
- Max. permissible relative humidity (operation) 75 % (on average, 85% infrequently, non-condensing)
- Rated control supply current IS typ. 60 mA
- Filter time max. 3 ms (Test pulse width of low test pulses)
- Input voltage range "0" signal 0 V DC ... 5 V DC
- Output name Enabling current paths
- Contact type 2 enabling current paths
- Sq. Total current 72 A2 (observe derating)
- Current max. 100 mA
- Delay time range 0.2 s ... 60 s ±5 % (can be set for 27/28)
- Degree of protection IP20
- Connection method Push-in connection
- Conductor cross-section flexible with ferrule and plastic sleeve 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6)
- Category 4
- Rated surge voltage/insulation Basic insulation 4 kV: between all current paths and housingSafe isolation, reinforced insulation 6 kV:between (A1, A2, S11, S12, S21, S22, S34, M1) and enabling current path (13/14)between (A1, A2, S11, S12, S21, S22, S34, M1) and enabling current path (
- REACh SVHC Lead 7439-92-1
- ECLASS 6.0 27371800
- ETIM 6.0 EC001449
- UNSPSC 19.0 39122205
- Ambient temperature (operation) -35 °C ... 60 °C (observe derating)
- Maximum altitude ≤ 2000 m (Above sea level)
- Input name Start circuit
- Output description PNP
- Switching voltage min. 12 V AC/DC
- Limiting continuous current 6 A (observe derating)
- Voltage approx. 23 V DC (US - 1 V)
- Restart time < 1 s (Boot time)
- Mounting position vertical or horizontal
- Housing material PBT
- Min. degree of protection of inst. location IP54
- Stop category 0
- Rated insulation voltage 250 V AC
- Shock 15g
- ECLASS 10.0.1 27371819
- ECLASS 7.0 27371819
- UNSPSC 18.0 39122205
- Protective circuit Surge protection Suppressor diode
- Max. permissible overall conductor resistance 150 Ω
- Number of outputs 1
- Maximum inrush current 500 mA (Δt = 1 ms at Us)
- Typical response time at US < 35 ms (automatic start)
- Net weight 126.45 g
- Assembly instructions See derating curve
- Conductor cross section flexible 0.2 mm² ... 1.5 mm²
- Conductor cross section solid 0.2 mm² ... 1.5 mm²
- Safety Integrity Level (SIL) 3
- Degree of pollution 2
- Vibration (operation) 10 Hz ... 150 Hz, 2g
- ECLASS 11.0 27371819
- ETIM 7.0 EC001449
- UNSPSC 13.2 39121501
- Current consumption < 3.2 mA (typically with US)
- Input current range "0" signal 0 mA ... 2 mA
- Limit frequency min. 0 Hz
- Mechanical service life 10x 106 cycles
- Output fuse 6 A gL/gG (N/O contact)
- Typical release time at US < 25 ms (when controlled via S12 (only for undelayed contact 13/14))
- Mounting type DIN rail mounting
- Status display 5 x bi-color LED
- Conductor cross-section flexible with ferrule without plastic sleeve 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6)
- Conductor cross-section AWG 24 ... 16
- Standards/regulations DIN EN 50178
- Overvoltage category III
- China RoHS Environmentally Friendly Use Period = 50 years
- ECLASS 5.0 27371900
- ECLASS 9.0 27371819
- UNSPSC 21.0 39122205
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Manufacturer warranty
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
Fast Shipping & Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Need more details?
Feel free to chat with us