Axioline F XC, Analog output module, Analog outputs: 8, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection method: 2-conductor, transmission speed in the local bus: 100 Mbps, Extreme condi
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Programmable Logic Controllers that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2701237 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Height 126.1 mm
- Degree of protection IP20
- Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
- Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
- Note on weight specifications with connectors and bus base module
- Number of interfaces 2
- Number of outputs 8
- Mounting position any (no temperature derating)
- Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
- Current consumption typ. 110 mA (8 voltage channels, 10 V output)
- Depth 54 mm
- Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
- Mounting type DIN rail
- Note on dimensions The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Net weight 260 g
- Connection method Push-in connection
- Power consumption typ. 1.725 W (to UBus and UA; power input; no load, output 0 V)
- Output name Analog outputs
- Data formats IB IL, S7-compatible
- Current output signal 0 mA ... 20 mA
- Permissible cable length max. 250 m (Reference cable type LiYCY (TP) n*2*0.5 mm²)
- Immunity to conducted interference Noise immunity test in accordance with EN 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
- Mechanical tests Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
- ECLASS 6.0 27242600
- ETIM 7.0 EC001596
- UNSPSC 7.0901 43201404
- UNSPSC 18.0 32151602
- UNSPSC 20.0 32151602
- Width 53.6 mm
- Ambient temperature (operation) -25 °C ... 60 °C (Standard)
- Color traffic grey A RAL 7042
- Designation Supply for analog modules (UA)
- Supply voltage 24 V DC
- Note regarding the connection technology shielded, twisted pair
- Type of protection Short-circuit and overload protection
- Test section 5 V supply of the local bus (UBus) / 24 V supply (I/Os) 500 V AC 50 Hz 1 min.
- Immunity to burst Noise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion B, 2 kV
- Protection class III (IEC 61140, EN 61140, VDE 0140-1)
- China RoHS Environmentally Friendly Use Period = 50 years
- ECLASS 5.0 27242200
- ETIM 3.0 EC001599
- ETIM 6.0 EC001596
- UNSPSC 13.2 32151602
- Permissible humidity (operation) 5 % ... 95 % (non-condensing)
- Representation of output values 16 bits (15 bits + sign)
- Protective circuit Surge protection electronic (35 V, 0.5 s)
- Process data update 300 µs
- Voltage output signal 0 V ... 5 V
- Precision typ. 0.1 % (of output range final value)
- Interference emission Noise emission test according to EN 61000-6-3 Class B
- ECLASS 10.0.1 27242601
- ECLASS 4.1 27240400
- UNSPSC 11 39121311
- UNSPSC 19.0 32151602
- Transmission speed 100 Mbps
- D/A conversion time 5 µs
- ECLASS 7.0 27242601
- ETIM 4.0 EC001435
- Immunity to surge Noise immunity test in accordance with EN 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 up to HW 01: Criterion B,DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical), ±1 kV to shielded I/O cables
- REACh SVHC Lead 7439-92-1
- ECLASS 5.1 27242600
- ECLASS 9.0 27242601
- UNSPSC 6.01 43172015
- UNSPSC 12.01 39121311
- UNSPSC 21.0 32151602
- Protective circuit/component electronic
- Immunity to ESD Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge
- ECLASS 4.0 27240400
- Load/output load voltage output > 2 kΩ
- Immunity to EF Noise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
- Degree of pollution 2 (IEC 60664-1, EN 60664-1)
- Load/output load current output to 500 Ω
- Connection technology 2-conductor
- Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
- D/A converter resolution 16 bit
- ECLASS 11.0 27242601
- Overvoltage category II (IEC 60664-1, EN 60664-1)
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Manufacturer warranty
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
Fast Shipping & Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Need more details?
Feel free to chat with us
What can I help you find today?