Axioline F, Temperature recording module, Analog inputs: 8 (8 inputs for thermocouples or linear voltage, plus 1 input -5 V to +5 V), connection method: 2-conductor (shielded, twisted pair), transmission speed in the local bus: 100 Mbps, degree of protect
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Programmable Logic Controllers that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2688417 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Supply voltage 24 V DC
- Height 126.1 mm
- Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
- Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
- Conductor cross section AWG max. 16
- Note on weight specifications with connectors and bus base module
- Note on dimensions The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).
- Degree of protection IP20
- Conductor cross section flexible min. 0.2 mm²
- Number 2
- Depth 54 mm
- Permissible humidity (operation) 5 % ... 95 % (non-condensing)
- Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
- Designation Supply for analog modules (UA)
- Width 53.6 mm
- Connection method Push-in connection
- Mounting type DIN rail
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Ambient temperature (operation) -25 °C ... 60 °C
- Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
- Conductor cross section solid max. 1.5 mm²
- Conductor cross section flexible max. 1.5 mm²
- Net weight 144 g
- Protective circuit Surge protection electronic (35 V, 0.5 s)
- Conductor cross section AWG min. 24
- Stripping length 8 mm
- Input name Analog inputs
- Measured value representation 16 bits (15 bits + sign bit)
- Conductor cross section solid min. 0.2 mm²
- Degree of pollution 2 (IEC 60664-1, EN 60664-1)
- Power consumption typ. 1.63 W (entire device)
- Connection technology 2-conductor (shielded, twisted pair)
- Input filter time 40 ms
- Test section 5 V supply of the local bus (UBus) / 24 V supply (I/Os) 500 V AC 50 Hz 1 min.
- Interference emission Noise emission test according to EN 61000-6-3 Class B
- ECLASS 10.0.1 27242601
- ECLASS 4.1 27240400
- ECLASS 7.0 27242601
- Transmission speed 100 Mbps
- Mounting position any (no temperature derating; Parameterize the mounting position using the object 0080hex ParaTable!)
- Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
- Sensor types that can be used (TC) U, T, L, J, E, K, N, S, R, B, C, W, HK
- A/D converter resolution 24 bit
- Color traffic grey A RAL 7042
- Current consumption typ. 45.3 mA
- Number of inputs 8 +1 mm (8 inputs for thermocouples or linear voltage, plus 1 input -5 V to +5 V)
- Measuring principle Sigma/Delta process
- Type of protection Short-circuit protection, overload protection of the inputs
- Sensor types (RTD) that can be used Pt 100 (4 external cold junctions, can also be used as a sensor input)
- Description of the input Inputs for thermocouples or linear voltage
- Immunity to ESD Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge
- Overvoltage category II (IEC 60664-1, EN 60664-1)
- ECLASS 4.0 27240400
- Immunity to burst Noise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion A for shielded cables, 2 kV
- ECLASS 5.1 27242600
- ETIM 3.0 EC001599
- ECLASS 9.0 27242601
- UNSPSC 11 39121311
- UNSPSC 19.0 32151602
- Immunity to conducted interference Noise immunity test in accordance with EN 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
- ECLASS 11.0 27242601
- ECLASS 6.0 27242600
- ETIM 6.0 EC001596
- UNSPSC 20.0 32151602
- Immunity to surge Noise immunity test in accordance with EN 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, supply lines DC: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical), ±1 kV to shielded I/O cables
- China RoHS Environmentally Friendly Use Period = 50 years
- ECLASS 5.0 27242200
- UNSPSC 7.0901 43201404
- UNSPSC 13.2 32151602
- UNSPSC 18.0 32151602
- Immunity to EF Noise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
- REACh SVHC Lead 7439-92-1
- Mechanical tests Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
- ETIM 4.0 EC001596
- ETIM 7.0 EC001596
- UNSPSC 21.0 32151602
- Protection class III (IEC 61140, EN 61140, VDE 0140-1)
- UNSPSC 6.01 43172015
- UNSPSC 12.01 39121311
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Manufacturer warranty
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
Fast Shipping & Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Need more details?
Feel free to chat with us
What can I help you find today?