2320911 Phoenix Contact AC/DC Power Supplies
Part#:2320911
Manufacturer:Phoenix Contact
Category:AC/DC Power Supplies
Product Lifecycle:Active
Get a quick Quote!
Primary-switched power supply unit, QUINT POWER, Screw connection, DIN rail mounting, SFB Technology (Selective Fuse Breaking), input: 1-phase, output: 24 V DC / 10 A
About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2320911 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Height with alternative assembly 130 mm
- Installation distance right/left 5 mm / 5 mm
- Current consumption 4 A (100 V AC)
- Type of protection Transient surge protection
- Selective Fuse Breaking (ISFB) 60 A (12 ms)
- POWER BOOST (IBoost) 15 A (-25 °C ... 40 °C permanent, UOUT = 24 V DC )
- Typical response time < 0.15 s
- Insulation voltage input / PE 3.5 kV AC (type test)
- Connection method Screw connection
- Screw thread M3
- EMC requirements for noise emission EN 61000-6-3
- Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204-1 (PELV)
- Explosive atmosphere EN 60079-15 (Zone 2)
- DeviceNet approval DeviceNet™ Power Supply Conformance Tested
- Electrostatic discharge EN 61000-4-2
- Electromagnetic HF field EN 61000-4-3
- Frequency range 0.15 MHz ... 80 MHz
- Input 2 kV (Test Level 3 - symmetrical)
- Signal 1 kV (Test Level 2 - asymmetrical)
- China RoHS Environmentally Friendly Use Period = 25;
- ECLASS 5.1 27049000
- ECLASS 9.0 27040701
- UNSPSC 7.0901 39121004
- UNSPSC 13.2 39121004
- UNSPSC 20.0 39121004
- Dielectric strength maximum 300 V AC
- Input fuse 10 A (slow-blow, internal)
- Protective circuit/component Varistor, gas-filled surge arrester
- Connection in series yes
- Maximum power dissipation in no-load condition 9.1 W
- Efficiency typ. 92.5 % (230 V AC)
- Mounting position horizontal DIN rail NS 35, EN 60715
- Conductor cross section solid min. 0.2 mm²
- Conductor cross section flexible max. 2.5 mm²
- Conductor cross section AWG max. 12
- EMC requirements for noise immunity EN 61000-6-1
- Standard - Equipment safety BG (design tested)
- UL approvals UL/C-UL listed UL 508
- SIQ BG (type approved)
- Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
- Test field strength 10 V/m (Test Level 3)
- Fast transients (burst) EN 61000-4-4
- Surge voltage load (surge) EN 61000-4-5
- REACh SVHC Lead 7439-92-1
- Voltage 10 V (Test Level 3)
- ECLASS 7.0 27049002
- UNSPSC 6.01 30211502
- UNSPSC 12.01 39121004
- Nominal power consumption 303 VA
- Recommended breaker for input protection 10 A ... 20 A (AC: Characteristics B, C, D, K)
- Setting range of the output voltage (USet) 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity)
- Connection in parallel Yes, for redundancy and increased capacity
- Protection against overvoltage at the output (OVP) ≤ 32 V DC
- Net weight 1.1 kg
- Insulation voltage output / PE 500 V DC (routine test)
- Nominal input voltage range 100 V AC ... 240 V AC
- Inrush current < 15 A
- Nominal output voltage 24 V DC ±1 %
- Feedback voltage resistance ≤ 35 V DC
- Control deviation < 1 % (change in load, static 10 % ... 90 %)
- MTBF (IEC 61709, SN 29500) > 940000 h (25 °C)
- Protection class I
- Conductor cross section flexible min. 0.2 mm²
- Standard - Electrical safety IEC 60950-1/VDE 0805 (SELV)
- HART FSK Physical Layer Test Specification Compliance Output voltage UOut compliant
- Rail applications EN 50121-4
- Mains variation/undervoltage SEMI F47-0706 Compliance Certificate
- Contact discharge 8 kV (Test Level 4)
- Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
- Comments Criterion A
- Criterion A Normal operating behavior within the specified limits.
- I/O/S asymmetrical
- ECLASS 10.0.1 27040701
- ETIM 4.0 EC000599
- ETIM 6.0 EC002540
- UNSPSC 18.0 39121004
- UNSPSC 21.0 39121004
- Discharge current to PE < 3.5 mA
- Mains buffering time typ. 36 ms (120 V AC)
- Nominal output current (IN) 10 A (-25 °C ... 60 °C, UOUT = 24 V DC)
- Derating 60 °C ... 70 °C (2.5%/K)
- Output power 240 W
- Power loss nominal load max. 22 W
- Insulation voltage input/output 4 kV AC (type test)
- Conductor cross section AWG min. 16
- Stripping length 7 mm
- Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
- Standard - Safe isolation DIN VDE 0100-410
- Standard – Limitation of mains harmonic currents EN 61000-3-2
- CSA CAN/CSA-C22.2 No. 60950-1-07
- Shipbuilding approval DNV GL (EMC B), ABS, LR, RINA, NK, BV
- Discharge in air 15 kV (Test Level 4)
- Output 1 kV (Test Level 2 - symmetrical)
- Conducted interference EN 61000-4-6
- Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
- ECLASS 11.0 27040701
- ECLASS 5.0 27049000
- UNSPSC 11 39121004
- ETIM 7.0 EC002540
- UNSPSC 19.0 39121004
- Depth 125 mm
- Degree of protection IP20
- AC frequency range 50 Hz ... 60 Hz
- Residual ripple < 50 mVPP (with nominal values)
- Height 130 mm
- Width with alternative assembly 122 mm
- Ambient temperature (operation) -40 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
- Installation height ≤ 5000 m
- Depth with alternative assembly 63 mm
- Degree of pollution 2
- ECLASS 4.0 27040700
- ECLASS 4.1 27040700
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Climatic class 3K3 (in acc. with EN 60721)
- Assembly instructions alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
- Width 60 mm
- Installation distance top/bottom 50 mm / 50 mm
- Max. permissible relative humidity (operation) 100 % (at 25 °C, non-condensing)
- Input voltage range 85 V AC ... 264 V AC
- Conductor cross section solid max. 2.5 mm²
- ECLASS 6.0 27049000
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Manufacturer warranty
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
Fast Shipping & Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Need more details?
Feel free to chat with us
What can I help you find today?