DIN rail diode module 48 V DC/2x20 A or 1x40 A. Uniform redundancy up to the consumer.

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Redundancy Modules that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2320160 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Depth
    125 mm
  • Climatic class
    3K3 (in acc. with EN 60721)
  • Installation distance top/bottom
    50 mm / 50 mm
  • Degree of pollution
    2
  • Maximum input current
    2x 30 A (-25°C ... 40°C)
  • Efficiency
    > 97 %
  • Conductor cross section solid min.
    0.5 mm²
  • Conductor cross section flexible max.
    16 mm²
  • Conductor cross section AWG max.
    6
  • Width
    50 mm
  • Installation distance right/left
    5 mm / 5 mm
  • Max. permissible relative humidity (operation)
    ≤ 95 % (at 25 °C, non-condensing)
  • Input voltage range
    30 V DC ... 56 V DC
  • Nominal output current (IN)
    40 A (Increasing power)
  • MTBF (IEC 61709, SN 29500)
    40000000 h
  • Mounting position
    horizontal DIN rail NS 35, EN 60715
  • Connection method
    Screw connection
  • Screw thread
    M4
  • EMC requirements for noise emission
    EN 61000-6-3
  • Standard - Safe isolation
    DIN VDE 0100-410
  • Surge voltage load (surge)
    EN 61000-4-5
  • ECLASS 5.0
    27371000
  • ECLASS 9.0
    27371010
  • UNSPSC 6.01
    30211502
  • UNSPSC 13.2
    32151504
  • Height
    130 mm
  • Ambient temperature (operation)
    -40 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
  • Installation height
    2000 m
  • Mains buffering time
    typ.
  • Net weight
    0.75 kg
  • Assembly instructions
    alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
  • Conductor cross section AWG min.
    10
  • Standard – Safety extra-low voltage
    IEC 60950-1 (SELV) and EN 60204-1 (PELV)
  • Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment
    EN 50178
  • Electromagnetic HF field
    EN 61000-4-3
  • ECLASS 10.0.1
    27371010
  • ECLASS 5.1
    27371000
  • ETIM 2.0
    EC001039
  • UNSPSC 11
    39121004
  • Degree of protection
    IP20
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Nominal input current
    2x 20 A (-25 °C ... 60 °C)
  • Derating
    60 °C ... 70 °C (2.5%/K)
  • Connection in series
    No
  • Protection class
    III
  • Conductor cross section flexible min.
    0.5 mm²
  • EMC requirements for noise immunity
    EN 61000-6-1
  • Standard - Electrical safety
    EN 60950-1/VDE 0805 (SELV)
  • Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
    EN 50178/VDE 0160 (PELV)
  • Fast transients (burst)
    EN 61000-4-4
  • Conducted interference
    EN 61000-4-6
  • ECLASS 7.0
    27371010
  • ETIM 6.0
    EC000683
  • UNSPSC 12.01
    39121004
  • UNSPSC 21.0
    32151504
  • Nominal input voltage range
    48 V DC
  • Nominal output voltage
    48 V DC
  • Power loss nominal load max.
    14 W (IOUT = 20 A)
  • Housing material
    Steel sheet, zinc-plated
  • Conductor cross section solid max.
    16 mm²
  • Stripping length
    10 mm
  • Insulation voltage input, output / housing
    1000 V
  • Electrostatic discharge
    EN 61000-4-2
  • Electromagnetic compatibility
    Conformance with EMC Directive 2014/30/EU
  • ECLASS 4.0
    27250300
  • ETIM 3.0
    EC001039
  • UNSPSC 7.0901
    39121004
  • UNSPSC 20.0
    32151504
  • UNSPSC 18.0
    32151504
  • UL approvals
    UL/C-UL listed UL 508
  • Low Voltage Directive
    Conformance with Low Voltage Directive 2014/35/EC
  • ECLASS 4.1
    27250300
  • ECLASS 11.0
    27371010
  • ECLASS 6.0
    27371000
  • ETIM 4.0
    EC002540
  • ETIM 7.0
    EC000683
  • UNSPSC 19.0
    32151504

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.


Manufacturer warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

Fast Shipping & Delivery


Secure Payment Processing


Warranty


Responsive Customer Support


Need more details?

Feel free to chat with us

What can I help you find today?