2320034 Phoenix Contact DC/DC Converters
Part#:2320034
Manufacturer:Phoenix Contact
Category:DC/DC Converters
Product Lifecycle:Active
Get a quick Quote!
Primary-switched QUINT DC/DC converter for DIN rail mounting with SFB (Selective Fuse Breaking) Technology, input: 24 V DC, output: 24 V DC/5 A
About the manufacturer: Phoenix Contact is one of the manufacturers that offers DC/DC Converters that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2320034 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Depth 125 mm
- Installation distance right/left (active) 15 mm / 15 mm (≤ 70 °C)
- Installation distance top/bottom 50 mm / 50 mm (≤ 70 °C)
- Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
- Nominal input voltage range 24 V DC
- Extended input voltage range in operation 14 V DC ... 18 V DC (Derating)
- Type of protection Transient surge protection
- Nominal output voltage 24 V DC ±1 %
- Nominal output current (IN) 5 A (-25 °C ... 60 °C)
- Connection in parallel Yes, for redundancy and increased capacity
- Connection in series yes
- Height 130 mm
- Depth with alternative assembly 35 mm
- Installation distance top/bottom (active) 50 mm / 50 mm (≤ 70 °C)
- Climatic class 3K3 (in acc. with EN 60721)
- Inrush current < 15 A (typical)
- Height with alternative assembly 130 mm
- Degree of protection IP20
- Ambient temperature (start-up type tested) -40 °C
- Width 32 mm
- Installation distance right/left 0 mm / 0 mm (≤ 70 °C)
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Input voltage range 18 V DC ... 32 V DC
- Current consumption 7 A (24 V, IBOOST)
- Recommended breaker for input protection 10 A ... 16 A (Characteristics B, C, D, K)
- Protective circuit/component Varistor
- POWER BOOST (IBoost) 6.25 A (-25 °C ... 40 °C permanent, UOUT = 24 V DC )
- Selective Fuse Breaking (ISFB) 30 A (12 ms)
- Protection against overvoltage at the output (OVP) < 35 V DC
- Feedback voltage resistance 35 V DC
- Power loss nominal load max. 11.4 W
- Net weight 0.7 kg
- Protection class III
- Conductor cross section solid max. 2.5 mm²
- Conductor cross section flexible min. 0.2 mm²
- Conductor cross section AWG max. 12
- Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
- Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
- UL approvals UL/C-UL listed UL 508
- Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
- Electromagnetic HF field EN 61000-4-3
- Comments Criterion A
- Width with alternative assembly 122 mm
- Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C derating, 2.5 %/K, startup at -40°C type-tested)
- Degree of pollution 2
- Mains buffering time > 10 ms (24 V DC)
- Input fuse 15 A (internal (device protection))
- Setting range of the output voltage (USet) 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
- Derating 60 °C ... 70 °C (2.5%/K)
- Max. capacitive load unlimited
- Control deviation < 1 % (change in load, static 10 % ... 90 %)
- Residual ripple < 20 mVPP
- Peak switching voltages nominal load < 10 mVPP (20 MHz)
- Insulation voltage input/output 1.5 kV (type test)
- Assembly instructions alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
- Conductor cross section solid min. 0.2 mm²
- Conductor cross section AWG min. 24
- Stripping length 7 mm
- EMC requirements for noise immunity EN 61000-6-1
- Standard - Safe isolation DIN VDE 0100-410
- Rail applications EN 50121-4
- Discharge in air 15 kV (Test Level 4)
- Frequency range 0.15 MHz ... 80 MHz
- Fast transients (burst) EN 61000-4-4
- Input 1 kV (Test Level 2 - symmetrical)
- Signal 1 kV (Test Level 2 - asymmetrical)
- Conducted interference EN 61000-4-6
- Voltage 10 V (Test Level 3)
- Criterion A Normal operating behavior within the specified limits.
- ECLASS 10.0.1 27210901
- ECLASS 11.0 27210901
- ECLASS 6.0 27210900
- ECLASS 4.1 27210900
- ECLASS 5.1 27210900
- ETIM 4.0 EC002542
- UNSPSC 6.01 30211502
- UNSPSC 7.0901 39121004
- UNSPSC 12.01 39121004
- UNSPSC 18.0 39121041
- UNSPSC 19.0 39121041
- Active current limitation Approximately 7.2 A
- Maximum power dissipation in no-load condition 2.4 W
- Efficiency > 92 %
- Mounting position horizontal DIN rail NS 35, EN 60715
- Connection method Pluggable screw connection
- Conductor cross section flexible max. 2.5 mm²
- Screw thread M3
- Standard – Safety extra-low voltage EN 60950-1 (SELV)
- EMC requirements for noise emission EN 61000-6-3
- Contact discharge 8 kV (Test Level 4)
- Shipbuilding approval DNV GL (EMC B)
- Electrostatic discharge EN 61000-4-2
- Test field strength 10 V/m
- Output 1 kV (Test Level 2 - symmetrical)
- Surge voltage load (surge) EN 61000-4-5
- I/O/S asymmetrical
- China RoHS Environmentally Friendly Use Period = 25;
- Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
- REACh SVHC Lead 7439-92-1
- ECLASS 4.0 27210900
- ECLASS 5.0 27210900
- ECLASS 7.0 27210901
- ECLASS 9.0 27210901
- ETIM 7.0 EC002046
- ETIM 6.0 EC002046
- UNSPSC 11 39121004
- UNSPSC 13.2 39121041
- UNSPSC 21.0 39121041
- UNSPSC 20.0 39121041
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Manufacturer warranty
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
Fast Shipping & Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Need more details?
Feel free to chat with us
What can I help you find today?