Primary-switched power supply unit, QUINT POWER, Push-in connection, input: 12 V DC - 24 V DC, output: 24 V DC / 2.5 A

About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at Power Resources International site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 1066714 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Weight
    0.246 kg
  • Typical current consumption
    typ. 7.2 A (12 V DC)
  • Inrush current integral (I2t)
    < 0.1 A2s
  • Insulation voltage input/output
    1.5 kV DC (type test)
  • Connection method
    Push-in connection
  • Standard - safety for equipment for measurement, control, and laboratory use
    IEC 61010-1
  • Standard – Limitation of mains harmonic currents
    EN 61000-3-2
  • Noise emission
    EN 55016
  • Discharge in air
    8 kV (Test Level 3)
  • Electromagnetic HF field
    EN 61000-4-3
  • Comments
    Criterion B
  • Surge voltage load (surge)
    EN 61000-4-5
  • I/O/S
    asymmetrical
  • Frequency
    60 Hz
  • Pulse-shape magnetic field
    EN 61000-4-9
  • Attenuated sinusoidal oscillations (ring wave)
    EN 61000-4-12
  • Attenuated oscillating wave
    EN 61000-4-18
  • Criterion B
    Temporary impairment to operational behavior that is corrected by the device itself.
  • Mains buffering
    typ. 14 ms (12 V DC)
  • Type test (IEC/EN 60950-1) A
    4 kV AC
  • Conductor cross section solid
    0.2 mm² ... 2.5 mm²
  • Conductor cross section AWG
    24 ... 14
  • Nominal output voltage (UN)
    24 V DC
  • Static Boost (IStat.Boost)
    3.125 A (≤ 40 °C)
  • Input voltage range
    12 V DC ... 24 V DC -25 % ... +33 % ()
  • Inrush current limitation typical
    8.6 A
  • Input fuse
    15 A (fast blow, internal)
  • Production test A
    3 kV AC
  • Stripping length
    10 mm
  • Conductor cross section flexible
    0.2 mm² ... 2.5 mm²
  • Setting range of the output voltage (USet)
    24 V DC ... 28 V DC (> 24 V DC, constant capacity)
  • Nominal output current (IN)
    2.5 A
  • Feedback voltage resistance
    ≤ 35 V DC
  • MTBF (IEC 61709, SN 29500)
    > 1347000 h (25 °C)
  • Temperature
    25 °C
  • Voltage
    300 V (1 s)
  • Main converter stage
    70 kHz ... 150 kHz (Main converter stage)
  • Protection class
    II
  • Width
    32 mm
  • Depth
    90 mm
  • Efficiency
    typ. 89.5 % (12 V DC)
  • Ambient temperature (operation)
    -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
  • Max. permissible relative humidity (operation)
    ≤ 95 % (at 25 °C, non-condensing)
  • Vibration (operation)
    < 15 Hz, ±2.5 mm amplitude; 15 Hz ... 100 Hz: 2.3 g 90 Min. (in accordance with IEC 60068-2-6)
  • Climatic class
    3K3 (in acc. with EN 60721)
  • EMC requirements for noise immunity
    EN 61000-6-1
  • Standard - Electrical safety
    IEC 61010-2-201 (SELV)
  • Standard - Safe isolation
    IEC 61558-2-16
  • Electromagnetic compatibility
    Conformance with EMC Directive 2014/30/EU
  • Contact discharge
    8 kV (Test Level 4)
  • Frequency range
    50 Hz ... 60 Hz
  • Input
    2 kV (symmetrical)
  • Signal
    2 kV (Test Level 4 - symmetrical)
  • Power frequency magnetic field
    EN 61000-4-8
  • Additional text
    Test Level 2
  • Voltage dips
    EN 61000-4-11
  • Test level 1
    16.67 Hz 50 Hz 60 Hz (Test Level 3)
  • Criterion C
    Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
  • Dynamic Boost (IDyn.Boost)
    5 A (≤ 60 °C (4,9 s))
  • Protection against overvoltage at the output (OVP)
    < 32 V DC
  • Output current
    2.5 A
  • Time
    432000 h
  • Auxiliary converter stage
    4 kHz ... 70 kHz (Auxiliary converter stage)
  • Degree of protection
    IP20
  • Inflammability class in acc. with UL 94 (housing / terminal blocks)
    V0
  • Height
    106 mm
  • Ambient temperature (start-up type tested)
    -40 °C
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Maximum altitude
    ≤ 5000 m (> 2000 m, observe derating)
  • Shock
    18 ms, 30g, in each space direction (according to IEC 60068-2-27)
  • Degree of pollution
    2
  • Overvoltage category EN 61010-1
    II (≤ 5000 m)
  • Standard - Safety of transformers
    EN 61558-2-16
  • Standard – Safety extra-low voltage
    IEC 61010-1 (SELV)
  • Conducted noise emission
    EN 55016
  • Electrostatic discharge
    EN 61000-4-2
  • Test field strength
    1000 A/m
  • Fast transients (burst)
    EN 61000-4-4
  • Output
    1 kV (Test Level 3 - symmetrical)
  • Conducted interference
    EN 61000-4-6
  • Voltage dip
    0 %
  • Number of periods
    0.5 / 1 / 5 / 50 periods
  • Asymmetrical conducted disturbance variables
    EN 61000-4-16
  • Test level 2
    16.67 Hz 50 Hz 60 Hz (Test Level 4)
  • Criterion A
    Normal operating behavior within the specified limits.
  • ECLASS 9.0
    27210901

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.


Manufacturer warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

Fast Shipping & Delivery


Secure Payment Processing


Warranty


Responsive Customer Support


Need more details?

Feel free to chat with us

What can I help you find today?